BS 7671 Guide · Section 11

Quick reference

The numbers and checklists you reach for most, on one page. Every table is a Tradefox summary: use it to jog your memory, then confirm the detail in the current edition before you sign anything.

Key dates for Amendment 4

DateWhat changedWhat it means on site
15 April 2026BS 7671:2018+A4:2026 publishedYou could design to A4 from this day
15 October 2026BS 7671:2018+A2:2022+A3:2024 withdrawnNew designs must follow A4
Designed before 15 October 2026Transitional allowanceWork designed to A2+A3 may be finished and verified to that version
From 15 October 2026Certificates and reportsNew designs state BS 7671:2018+A4:2026 on the paperwork
Any timeOlder installationsNot unsafe just because the standard moved on; no automatic upgrade needed

Regulation references: BS 7671:2018+A4:2026 introduction (dates and transitional note). Full guide: What changed in Amendment 4

Maximum disconnection times (230 V)

CircuitTN systemTT system
Final circuit up to 63 A with socket-outlets, or up to 32 A feeding only fixed equipment0.4 s0.2 s
Distribution circuit, or any other final circuit5 s1 s

RCD test on site: one AC test at the rated residual current (IΔn), whatever the RCD type. A general non-delay device must trip within 300 ms; a time-delayed S-type between 130 ms and 500 ms. The old 5 × IΔn test is no longer required.

On site: on a TT installation the electrode resistance is usually too high for a fuse or MCB to clear a fault in time. That is why an RCD normally does the fault protection job on TT.

Regulation references: 411.3.2.2, 411.3.2.3, 411.3.2.4, Table 41.1, 415.1.1, 643.8. Full guide: Protection against electric shock

Where a 30 mA RCD is needed

WhereRequirementCan it be left off?
Socket-outlets rated up to 32 A30 mA additional protectionOnly outside dwellings, for sockets ordinary persons and children aren’t likely to use, and only with a documented risk assessment
Mobile equipment up to 32 A used outdoors30 mA additional protectionNo
AC final circuits feeding luminaires in dwellings30 mA additional protectionNo
Cables in walls or partitions less than 50 mm deep, or in partitions with metal partsUnder 50 mm: safe zone plus 30 mA RCD. Metal-part walls: 30 mA RCD at any depth (and a safe zone if shallow). Or a 522.6.204 method insteadYes, if the cable has an earthed metal covering, is in earthed metal conduit, or is SELV/PELV. Check Table 52.1
Rooms with a bath or showerEvery circuit serving the roomNo
Outdoor lighting the public can reach (street furniture and similar)30 mA additional protectionOnly if supplied by SELV

Regulation references: 411.3.3, 411.3.4, 522.6 and Table 52.1, 701.411.3.3, 714.411.3.4. Full guide: Protection against electric shock

Choosing the RCD type

TypeWhat it can senseTypical loads
ACPlain AC residual current onlyFixed equipment known to produce no DC, such as simple resistive heaters
AAC plus pulsating DCGeneral domestic circuits: LED lighting, IT equipment, most appliances
FEverything Type A senses, plus mixed-frequency currentSingle-phase variable-speed kit: heat pumps, air conditioning, modern washing machines
BEverything Type F senses, plus smooth DCThree-phase drives and inverters; some PV, battery and EV set-ups

When RCDs are in series, the upstream device must not be blinded by DC that a downstream device lets through:

  • No Type AC upstream of Type A, F or B.
  • No Type A upstream of Type F or B.
  • No Type F upstream of Type B.

The one exception: a Type AC, A or F RCD may sit upstream of a Type B where the RCD manufacturer specifically declares the arrangement suitable. This comes from an informative note to Regulation 531.3.3, so check it and Figure A53.2 in your copy.

Watch out: an EV charge point needs protection against DC fault current above 6 mA. If the charger doesn’t provide it, fit a Type B RCD, or a Type A or F with a separate DC detection device.

Regulation references: 531.3.3, Figure A53.2, 722.531.3.101. Full guide: Protection against electric shock et EV, solar, batteries and heat pumps

Where AFDDs are required

The rule applies to single-phase AC final circuits supplying socket-outlets rated up to 32 A. Use AFDDs to BS EN 62606.

PremisesAFDD on those socket circuits
High-rise residential: a domestic building with any storey more than 18 m above groundRequired
Houses in multiple occupation (HMOs)Required
Purpose-built student accommodationRequired
Care homesRequired
All other premisesRecommended
EV charge-point circuits to BS EN 61851 with BS EN IEC 62196-2 connectorsNot required

Regulation references: 421.1.7, 722.421.1.7.201. Full guide: Fire, arc fault and surge protection

Insulation resistance

CircuitTest voltage (DC)Minimum reading
SELV and PELV250 V0.5 MΩ
Up to 500 V, including FELV (normal 230/400 V work)500 V1 MΩ
Above 500 V1000 V1 MΩ
On site: if an SPD or sensitive kit can’t be disconnected, you may test that circuit at 250 V DC. The 1 MΩ minimum still applies. A new circuit that only just passes deserves a closer look.

Regulation references: 643.3, Table 64. Full guide: Inspection and testing

Voltage drop limits

Installation fed from the public LV networkLimitAt 230 V
Eclairage3%6.9 V
Other uses (power, heating)5%11.5 V

Limits are measured from the origin of the installation to the furthest point. Installations on a private supply are allowed more; check Table 4Ab for the figures.

Regulation references: Section 525, Appendix 4 (Table 4Ab). Full guide: Cable selection and sizing

Main protective bonding: minimum copper sizes

Supply arrangementMinimum main bonding conductor
Not PME (TN-S, TT)Half the earthing conductor size, never below 6 mm²; need not exceed 25 mm²
PME, supply neutral 35 mm² or less10 mm²
PME, supply neutral 50 mm²16 mm²
PME, supply neutral 70 mm²25 mm²
PME, larger suppliesCheck Table 54.8
Watch out: the network operator can ask for a bigger bonding conductor than the minimum. Check their requirements before you buy the cable.

Regulation references: 544.1.1, Table 54.8. Full guide: Earthing and bonding

EICR observation codes

CodeMeaningWhat happens next
C1Danger present, risk of injury nowAct straight away; make safe before you leave if you can
C2Potentially dangerousUrgent remedial work
C3Improvement recommendedNot dangerous; the report can still be satisfactory
FIFurther investigation advisedAdvisory under A4: on its own, an FI does not make the report unsatisfactory. Use it rarely, and never for things you can code, such as low insulation resistance or an unidentified circuit.

In privately and socially rented homes in England, landlords must get remedial or investigative work done within 28 days, or sooner if the report says so. GOV.UK guidance still treats FI as needing investigation, so tell landlords to follow every FI up.

Regulation references: 653.1, 653.2, Appendix 6. Full guide: Certificates and EICR codes

Pre-energisation checklist

Do these with the supply off, in this order, before anything goes live:

  1. Inspection complete: terminations tight, barriers fitted, cables supported, labels on.
  2. Continuity of protective conductors, including main and supplementary bonding.
  3. Ring final circuits: end-to-end and cross-connected readings.
  4. Insulation resistance at the right test voltage, sensitive kit disconnected.
  5. Polarity: switches and single-pole devices in the line conductor only.
  6. Earth electrode resistance on TT installations.
  7. Only then energise, and move on to Ze, Zs, fault current, RCD and functional tests.

Regulation references: Chapter 64, Section 643. Full guide: Inspection and testing

Safe isolation checklist

  1. Identify the right circuit and the right isolation point.
  2. Switch off and isolate.
  3. Lock off, keep the key on you, and fit a warning label.
  4. Prove your voltage indicator works on a known live source or proving unit.
  5. Test dead between every combination of line, neutral and earth.
  6. Prove the indicator again, straight after the dead test.
  7. Only now start work.
Watch out: a multimeter or non-contact tester is not a substitute for a two-pole voltage indicator with probes that meet HSE GS38.

Regulation references: Section 537 (isolation and switching); Electricity at Work Regulations 1989, regulations 12 and 13. Full guide: Inspection and testing