Fire extinguishers.Right colour, right fire.

What the colours and class letters on a fire extinguisher mean in the UK, Europe, North America, Australia and beyond, which type is safe on which fire, and how to use one without putting yourself at risk.

WATERMISTFOAMPOWDERCO₂WET CHEM
UK extinguishers are all red. A small colour zone shows what is inside.

Classes of fire. Same fire, different letter.

Fires are grouped by what is burning, but the letters do not line up between regions. A US “C” is an electrical fire; a UK or Australian “C” is burning gas. Always read the letter in the context of the label it is on.

Swipe the table sideways to see every region.

Fire class letters for the same fuel in different regions
What is burningUK and EuropeUSA and CanadaAustralia and NZIndiaJapan
SolidsWood, paper, textiles, many plasticsAAAAAAAAordinary
Flammable liquidsPetrol, diesel, paint, solventsBBBBBBBBoil
Flammable gasesLPG, methane, acetyleneCCPart of BCCCCNo classCheck local rules
MetalsMagnesium, sodium, lithium, aluminium swarfDDDDDDDNo classCheck local rules
ElectricalLive equipment and wiringNo letter, symbolCEENo letterElectrical
Cooking oils and fatsDeep-fat fryers, chip pansFFKKFFNot in IS 15683Check local rulesCounted as oilCheck local rules
  1. London Fire Brigade – Guidance Note 08: portable fire extinguishers (opens in a new tab)Signal red bodies; colour zone of up to 5% of the surface; zone colours (cream foam, blue powder, black CO2, canary yellow wet chemical, green clean agent, violet Class D powder); BS EN 2 classes A, B, C, D, F; annual basic service
  2. OSHA eTool – Extinguisher basics (opens in a new tab)US classes A, B, C (electrical), D, K; water for A only; CO2 for B and C; never water on electrical or flammable-liquid fires; no water or CO2 on deep-fat fryers; water units have a silver body
  3. OSHAcademy – Fire prevention plans: classes of fire (opens in a new tab)US Class B includes flammable gases and aerosols
  4. Queensland Fire Department – Fire extinguishers information sheet (opens in a new tab)AS/NZS 1841 colour bands: red water, blue foam, white powder, black CO2, yellow vaporising liquid, oatmeal wet chemical; classes A to F with E for electrical; PASS
  5. Masterspec NZ – Fire extinguishers: matching the hazard (opens in a new tab)AS/NZS 1841.1 band colours used in New Zealand; classes A to F per AS/NZS 1850; NZS 4503 class symbols
  6. Bureau of Indian Standards – IS 15683:2006 Portable fire extinguishers (public copy) (opens in a new tab)Red body to shade 536 or 538 of IS 5 (cl. 10.1); classes A, B, C, D (cl. 3.1); use-code symbols with red slash for unsuitable classes
  7. Fire and Disaster Management Agency (Japan) – 2010 revision of extinguisher technical standards (opens in a new tab)From 1 Jan 2011 extinguishers show ordinary, oil and electrical fire pictograms on white, yellow and blue grounds; old-standard units allowed until 31 Dec 2021
  8. City of Okayama – Extinguisher installation standard (opens in a new tab)Capacity units are stated separately for A (ordinary) and B (oil) fires

Checked 9 Nov 2026

By region. How each system marks the agent.

Pick a region to see its extinguishers drawn out, the standards behind them and where each fact comes from. On-screen colours are approximate.

United Kingdom

BS EN 3 with BS 5306-10 colour zones

Verified

Every new extinguisher is red. A small colour zone on the upper front of the body, plus the label, tells you what is inside. The UK code of practice is generally described as asking for a zone of 3% to 10% of the surface, with at least 90% of the body left red. BS EN 3-7 itself allows a zone of up to about 5%.

Construction
BS EN 3 (parts 7 to 10)
Colour coding
BS 5306-10:2019 (replaced BS 7863)
Fire classes
BS EN 2: A, B, C, D, F
Servicing
BS 5306-3
Body colour
Signal red on every type. Older units painted all over in the agent colour are still legal until replaced.

What you will see

WATER
WaterNone, all redSuits: A
MIST
Water mistWhiteSuits: A, B, C, F, electrical (tested models)
FOAM
Foam (AFFF)CreamSuits: A, B
POWDER
ABC powderBlueSuits: A, B, C, electrical
CO₂
CO₂BlackSuits: B, electrical
WET CHEM
Wet chemicalYellowSuits: F, A
D POWDER
Class D powderBlue (or violet)Suits: D only

Electrical fires are not a separate class in BS EN 2. Suitable units carry an electrical symbol and a note on any dielectric test it has passed. Halon (green) has been banned since 2003 except for aviation and military uses. London Fire Brigade guidance gives violet for Class D powder; many makers simply use blue and label it for metal fires.

  1. London Fire Brigade – Guidance Note 08: portable fire extinguishers (opens in a new tab)Signal red bodies; colour zone of up to 5% of the surface; zone colours (cream foam, blue powder, black CO2, canary yellow wet chemical, green clean agent, violet Class D powder); BS EN 2 classes A, B, C, D, F; annual basic service
  2. BSI Knowledge – BS 5306-10:2019 colour coding of portable fire extinguishers (opens in a new tab)BS 5306-10:2019 is the current UK code of practice for the colour, size and position of the agent colour zone; extinguishers made to the withdrawn BS 7863 remain acceptable
  3. BSI Knowledge – BS 7863:1996 (withdrawn) (opens in a new tab)BS 7863 was the earlier UK colour-coding recommendation and has been withdrawn
  4. NBS – Fire extinguisher types: choose, identify, maintain and use (opens in a new tab)Red body with a zone of about 5% under BS EN 3; water mist white and red; suitability by class; older units fully colour coded
  5. Firesafe.org.uk – Fire extinguishers: classes, colour coding, rating and maintenance (opens in a new tab)Agent colours incl. white for water mist; suitability of each type by class; electrical use of CO2, powder and dielectrically tested foam or mist; five-yearly discharge of water, foam and powder; ten-yearly CO2 refurbishment
  6. Fire Protection Shop – Fire extinguisher guide (PDF) (opens in a new tab)UK colour zone of 3% to 10% of the surface, at least 90% red, placed on the upper front; water units all red
  7. BAFE – How often should I be servicing my fire extinguishers? (opens in a new tab)BS 5306-3 intervals: monthly user check, 12-monthly basic service, 5-yearly extended service for water-based and powder, 10-yearly overhaul for CO2 and clean agent

Checked 9 Nov 2026

Which extinguisher. Which fire.

General suitability of each extinguisher type against each class, using UK letters with the US equivalents in brackets. The label on the unit in front of you always overrides this table.

Swipe the table sideways to see every class.

Which extinguisher type can be used on which class of fire
ExtinguisherASolidsBLiquidsCGasesDMetalsFCooking oil (US K)EElectrical (US C)
WaterUK zone: RedYesNoNoNeverNeverNever

Never on electrical equipment, cooking oil or burning metal: water conducts, and on hot oil it flashes to steam and throws burning fat out.

Water mistUK zone: WhiteYesSome modelsSome modelsNoSome modelsSome models

Only the classes printed on the label. Electrical use only on dielectrically tested models.

FoamUK zone: CreamYesYesNoNoNoSome models

Electrical use only if the unit passed the dielectric test, and only from the stated distance.

ABC powderUK zone: BlueYesYesYesNoNoYes

Cuts visibility and can be breathed in. Avoid in small rooms. Does not cool, so fires can reignite.

CO₂UK zone: BlackNoYesNoNoNeverYes

No lasting cooling on solids. Never on a fat fryer. Displaces oxygen in small spaces and the horn gets very cold.

Wet chemicalUK zone: YellowYesSome modelsNoNoYesNo

Made for fryers: forms a soap-like crust on the oil. Apply gently; do not use on live equipment.

Class D powderUK zone: Blue / violetNoNoNoYesNoNo

Only for the metal named on the label. Lay it on gently to smother; never use water on a metal fire.

Never water on electricsWater conducts. Using it on live equipment can electrocute you.
Never water on a fat fireIt turns to steam under the oil and throws burning fat across the room.
Never CO₂ on a fryerIt can make burning oil erupt and spread, and it does not cool the oil enough to stop it reigniting.
Never water on burning metalMany metals react violently with water. Use only the Class D powder named for that metal.
  1. Firesafe.org.uk – Fire extinguishers: classes, colour coding, rating and maintenance (opens in a new tab)Agent colours incl. white for water mist; suitability of each type by class; electrical use of CO2, powder and dielectrically tested foam or mist; five-yearly discharge of water, foam and powder; ten-yearly CO2 refurbishment
  2. NBS – Fire extinguisher types: choose, identify, maintain and use (opens in a new tab)Red body with a zone of about 5% under BS EN 3; water mist white and red; suitability by class; older units fully colour coded
  3. London Fire Brigade – Guidance Note 08: portable fire extinguishers (opens in a new tab)Signal red bodies; colour zone of up to 5% of the surface; zone colours (cream foam, blue powder, black CO2, canary yellow wet chemical, green clean agent, violet Class D powder); BS EN 2 classes A, B, C, D, F; annual basic service
  4. OSHA eTool – Extinguisher basics (opens in a new tab)US classes A, B, C (electrical), D, K; water for A only; CO2 for B and C; never water on electrical or flammable-liquid fires; no water or CO2 on deep-fat fryers; water units have a silver body
  5. Bureau of Indian Standards – IS 15683:2006 Portable fire extinguishers (public copy) (opens in a new tab)Red body to shade 536 or 538 of IS 5 (cl. 10.1); classes A, B, C, D (cl. 3.1); use-code symbols with red slash for unsuitable classes

Checked 9 Nov 2026

Get out first. Fight only if it is safe.

An extinguisher is for a small fire that has only just started, and for helping people get out. It is never worth your life, and in most workplaces only trained staff should use one.

Raise the alarm

Shout “Fire!”, set off the nearest call point and make sure the fire service is called: 999 or 112 in the UK, 112 in Europe, 911 in North America, 000 in Australia. Do this before you pick up an extinguisher.

Check before you fight

  • The fire is small and in its very early stage
  • You have the right type for what is burning
  • Your way out is behind you and clear of smoke
  • You have been shown how to use it

Know when to leave

  • The fire is spreading or growing
  • Smoke is building up or your exit is threatened
  • The extinguisher runs out and the fire is not out
  • You have any doubt at all

Isolate the electrics

If equipment is involved, switch it off or isolate the supply if you can reach the switch safely. Use CO₂, powder or a unit tested for electrical use. Once the power is off, what is left burning is an ordinary A or B fire.

Kitchen fires

Turn off the heat only if you can do it safely. Use a wet chemical (Class F or K) extinguisher on fryers and pans of oil, applied gently. In commercial kitchens, let the hood suppression system operate first.

Small rooms

CO₂ pushes out the air you breathe and powder makes it hard to see. After using either in a small space, get out and ventilate before going back in.

Use it with PASS.

Stand a few metres back, with your exit behind you.

  1. Pull

    Pull out the safety pin. This breaks the tamper seal.

  2. Aim

    Point the nozzle or horn low, at the base of the flames. Hold a CO₂ horn by its handle only: it gets cold enough to burn skin.

  3. Squeeze

    Squeeze the lever steadily to release the agent. Let go to stop.

  4. Sweep

    Sweep from side to side across the base until the fire looks out. Back away, watch it, and be ready to go again or leave.

  1. OSHA eTool – Fire extinguisher use (PASS) (opens in a new tab)PASS technique; fight only an incipient fire after raising the alarm with a clear escape route; leave if in doubt
  2. OSHA eTool – Extinguisher basics (opens in a new tab)US classes A, B, C (electrical), D, K; water for A only; CO2 for B and C; never water on electrical or flammable-liquid fires; no water or CO2 on deep-fat fryers; water units have a silver body
  3. Queensland Fire Department – Fire extinguishers information sheet (opens in a new tab)AS/NZS 1841 colour bands: red water, blue foam, white powder, black CO2, yellow vaporising liquid, oatmeal wet chemical; classes A to F with E for electrical; PASS
  4. Firesafe.org.uk – Fire extinguishers: classes, colour coding, rating and maintenance (opens in a new tab)Agent colours incl. white for water mist; suitability of each type by class; electrical use of CO2, powder and dielectrically tested foam or mist; five-yearly discharge of water, foam and powder; ten-yearly CO2 refurbishment

Checked 9 Nov 2026

Servicing. Checked, not just hung up.

In the UK, BS 5306-3 sets out who checks what and when. The responsible person makes the monthly checks; the rest needs a competent engineer, such as one from a BAFE-registered company.

  1. MonthlyUser check

    In its place, not blocked, seal and pin intact, gauge in the green, no damage, instructions readable.

  2. Every 12 monthsBasic service

    Full inspection by a competent person, with the service label and records updated.

  3. Every 5 yearsExtended service

    Water-based and powder units are discharged, checked inside and refilled.

  4. Every 10 yearsOverhaul

    CO₂ and clean-agent units get a full overhaul by a competent engineer.

Recharge any extinguisher after use, even a short burst. Elsewhere: the US and Canada follow NFPA 10 (monthly inspection, annual maintenance and periodic hydrostatic tests); Australia follows AS 1851, with six-monthly inspection and yearly and five-yearly service.

  1. BAFE – How often should I be servicing my fire extinguishers? (opens in a new tab)BS 5306-3 intervals: monthly user check, 12-monthly basic service, 5-yearly extended service for water-based and powder, 10-yearly overhaul for CO2 and clean agent
  2. Fire Industry Association – Short guide to BS 5306-3:2017 (opens in a new tab)BS 5306-3:2017 sets broadly annual basic and broadly five-yearly extended servicing by competent persons
  3. London Fire Brigade – Guidance Note 08: portable fire extinguishers (opens in a new tab)Signal red bodies; colour zone of up to 5% of the surface; zone colours (cream foam, blue powder, black CO2, canary yellow wet chemical, green clean agent, violet Class D powder); BS EN 2 classes A, B, C, D, F; annual basic service
  4. Government of Alberta – STANDATA fire code interpretation 19-FCI-009 (opens in a new tab)National Fire Code of Canada applies NFPA 10 for selection, installation, inspection and maintenance; rating to CAN/ULC-S508; bilingual ULC labels required; monthly inspection, yearly maintenance
  5. Australian Maritime Safety Authority – Inspection of portable fire extinguishers (opens in a new tab)AS 1851 requires six-monthly inspection, with yearly and five-yearly service by an accredited provider

Checked 9 Nov 2026