Testing and verification
Ring continuity: equal line and neutral
- where
- reading at each point with ends cross-connected (Ω)
- line end-to-end resistance (Ω)
- neutral end-to-end resistance (Ω)
Explain this equation
Gives the reading you should get at each socket on a ring final circuit when the line and neutral ends are cross-connected. Use it to confirm the ring is complete and has no interconnections.
r1 is the end-to-end resistance of the line conductor and rn that of the neutral, each measured between the two ends of the ring. R_cross is the expected line-to-neutral reading at any point with the ends cross-connected.
Cross-connecting the ends turns the ring into a figure of eight. At any point the meter sees two equal paths in parallel, each (r1 + rn)/2. Two equal paths in parallel halve that again, giving a quarter of the sum, and it stays the same all the way round.
r1 and rn of 0.4 Ω each give 0.2 Ω at every socket. Readings should be substantially the same throughout; a higher reading at one point suggests a spur or a poor connection.
Watch out: this needs line and neutral of the same size, so r1 equals rn, and the calculator checks for that. Line-to-CPC readings with a smaller CPC use r2 instead. This is a dead test only.
For an intact uniform ring with equal line and neutral resistances, opposite-end cross-connections give two equal resistance paths in parallel at every point. Their combined resistance is one quarter of the sum of the end-to-end values.
This lesson concerns line-neutral readings with r1 = rn. CPC combinations with unequal conductor resistance do not generally give a perfectly constant reading around the ring.
Enter your values to see the result.
Common mistake
Claiming the same exact quarter-sum at every line-CPC point when conductor sizes differ.
Limits
Ideal ring without spurs or parallel paths; dead testing only. This calculation does not replace the complete ring test procedure and interpretation.