Technical reference: BS 7671:2018+A4:2026. Apply the current standard, equipment instructions and statutory duties relevant to the work and jurisdiction.
Loose and badly made terminations are a leading cause of heat damage in boards and accessories. This guide covers the hands-on part: reading the terminal data, preparing the conductor, crimping ferrules and torquing correctly. For the regulations behind it, see our cable selection and sizing reference and the Amendment 4 changes.
The conductor, terminal, any ferrule or lug, the tool and the method all have to match. There is no rule that every conductor gets a ferrule, that tighter is better, or that flex can be treated like solid cable. The terminal data sheet decides.
Termination selection record
| Item | Check |
|---|---|
| Conductor | Material, class, size and condition |
| Terminal | Permitted conductor types, sizes and quantities |
| End treatment | Ferrule or lug suitability where applicable |
| Tool | Correct preparation crimping or torque arrangement |
| Finished connection | Insertion, clamping, identification and support |
Identify the conductor class
Conductor construction affects how it behaves in a terminal. A solid conductor, a stranded rigid conductor and a fine-stranded flexible conductor do not respond identically to clamping. The installer should identify the conductor class and check that the terminal accepts it in the proposed size and configuration. Cross-sectional area alone does not establish compatibility.
Amendment 4 amends Regulation 526.2 so the connection method must suit the conductor class listed in Table 52.4. Regulation 526.9.1 requires fine strands not to be split or spread: use a terminal designed for that class or treat the end, usually with a crimped ferrule. Many screw terminals on accessories are only rated for Class 1 and 2, so check before you put flex in them. [3]
Read the terminal capacity correctly
Read the terminal data for the exact conductor configuration. Check material, class, cross-sectional area, end treatment and the permitted number of conductors. A terminal's stated maximum size for one untreated rigid conductor does not automatically authorise the same size of ferruled flexible conductor, or two smaller conductors inserted together. [1] [5]
Worked example (illustrative values). A typical MCB data sheet might list:
| Data sheet line | Illustrative value | What it tells you |
|---|---|---|
| Terminal capacity, rigid | 1 to 25 mm² | Class 1 and 2 conductors, one per terminal unless stated |
| Terminal capacity, flexible | 1 to 16 mm² | Class 5 limit, often lower than rigid; check with or without ferrule |
| Tightening torque | 2.0 to 2.5 N·m | Set your driver inside this range |
| Screw head | PZ2 / flat | Use the matching bit so it does not cam out |
| Strip length | 12 to 14 mm | Bare conductor or ferrule sleeve length to suit |
These numbers only show how to read a sheet. Your device will be different, and top and bottom terminals, busbar terminals and neutral bars can each have their own values, so always read yours. If two conductors must go in one terminal, the sheet must say that is allowed, and for what sizes. If not, use a suitable link or distribution block.
Prepare conductors without introducing damage
Insulation removal should leave the conductor suitable for the intended connection. Nicked solid conductors, severed strands and excessive exposed copper can undermine the termination. Preparation needs the correct stripping length and an appropriate tool, with the manufacturer's instructions used where the connector specifies a particular dimension or method.
The inspection should confirm that insulation has not entered the contact area and that bare conductor is not exposed beyond the permitted arrangement. Bending and dressing should not impose damaging stress at the point of entry. Where a conductor has been damaged, hiding the defect inside a connector is not an acceptable repair. The connection must be remade using a suitable undamaged section or another properly designed solution.
Use ferrules where the connection system requires them

Photo: Simon A. Eugster. Wire ferrule crimped.jpg. CC BY-SA 3.0. Resized where necessary and converted to WebP. No cropping, retouching or content changes.
Ferrules are one possible means of preparing a fine-stranded conductor. They are not a universal requirement, and some terminals accept the relevant untreated flexible conductor directly. Check the exact terminal's data before adding a ferrule. A collar can obstruct insertion, while the sleeve can increase the effective diameter enough to change the permitted conductor range. [1] [5]
Sizing and crimping a ferrule:
- Size: match the ferrule to the conductor area (0.5, 0.75, 1.0, 1.5, 2.5, 4, 6 mm² and up). Read the size printed on the box. Colour codes differ between systems (for example DIN and French codes), so colour alone does not tell you the size.
- Length: pick a sleeve length that matches the terminal strip length and clamp depth, commonly 8, 10, 12 or 18 mm. Too short and the screw bites bare strands; too long and copper is left exposed.
- Two conductors: use a twin-entry ferrule sized for both, and only where the terminal allows it.
- Tool: use a ratchet crimper that will not release until the full cycle is complete, with the profile (square, trapezoidal or hexagonal) the terminal maker accepts. Pliers are not a crimp tool.
- Check: all strands inside the sleeve, none folded back, insulation seated in the collar, collar not stopping full insertion.
A squashed sleeve is not proof of a good crimp. If in doubt, cut it off and redo it. [5] [6]
Apply the specified tightening torque

Using the example data sheet above, a terminal rated 2.0 to 2.5 N·m:
- Confirm which terminal the value is for. Line, load and busbar terminals can differ.
- Set a calibrated torque screwdriver inside the range, for example 2.2 N·m. Do not set it to the maximum.
- Fit the right bit, hold the driver square to the screw and tighten steadily until the driver clicks or slips. Stop at the first click.
- If the data is in lbf·in, convert it: 1 lbf·in ≈ 0.113 N·m, so 20 lbf·in ≈ 2.26 N·m.
- Mark or record the terminal as torqued if your company procedure asks for it.
Under-tightening leaves poor contact pressure and causes heating. Over-tightening damages the terminal and crushes the conductor. Similar-looking screws on different products can need different values. Values for common devices are collected in our torque settings reference, but the manufacturer’s sheet takes priority.
Look after the tool. Have the torque driver calibrated or checked at the interval set by its maker or your company (often yearly) and check the date before you use it. Use it within its working range; accuracy is usually poorest at the bottom of the scale. Follow the maker’s storage instructions. Shear-head connectors are tightened until the head shears, so do not apply a torque-driver routine to them. Only re-check or re-torque a terminal where the manufacturer requires it. Repeated re-tightening can deform conductors and damage terminals. [4]
Treat spring connections as a different system
A spring-operated terminal has its own preparation, insertion and inspection requirements. It should not be assessed by applying the habits used for a screw terminal. The correct stripping length, permitted conductor types and any operating tool need to be established from the product instructions. A conductor appearing to enter the opening is not proof that it is correctly retained.
Where a product provides inspection windows or other checking features, use them as intended. Check that the conductor has reached the required position and that insulation is correctly located. Do not modify a connector to accept an unsupported conductor or mix components from unrelated systems. Reliable performance depends on using the connection method within the conditions for which it was designed.
Coordinate cable support and enclosure space
Terminals should not be expected to carry mechanical loads that the cable support or strain relief should control. Cable entries, gland arrangements, bend radii and dressing need to leave the connection secure without excessive force. Crowded enclosures can make correct assembly and inspection difficult, especially where several larger conductors terminate close together.
The designer and installer should review space before the final assembly stage. A conductor that fits within a closed enclosure may still be bent too tightly or push another connection out of position. Covers should be fitted without trapping cables or placing pressure on terminals. If the arrangement cannot be installed and inspected properly, the enclosure or connection design needs reconsideration rather than more force during closure.
Inspect workmanship before energisation
Before covers go on, check each termination:
- conductor class suits the terminal, with ferrule where needed
- fully inserted, with no insulation under the clamp and no bare copper showing beyond the terminal
- no nicked solid conductors or cut strands
- torqued to the stated value
- identified, supported and not under strain from the cable
A continuity reading confirms an electrical path under the test conditions; it does not independently establish contact pressure, crimp quality or behaviour at full load. Similarly, a generic tug on a conductor is not a universal acceptance test. Use the product's prescribed checks and correct any defect before barriers or covers prevent inspection. Do not energise equipment merely to see whether a doubtful connection becomes hot.
Example of a flexible conductor substitution

Photo: SeanMiller. Crimp Tool For Bootlace Ferrules.jpg. CC BY-SA 4.0. Resized where necessary and converted to WebP. No cropping, retouching or content changes.
Replacement equipment has flexible conductors where the previous unit used rigid conductors. Before reusing the terminals, establish the new conductor class and check the permitted untreated or ferruled range. If a ferrule is proposed, check the sleeve length, crimp profile and collar clearance as well as cross-sectional area. Replace or adapt the connection only through a suitable documented arrangement.
Do not tin flex ends to stop them spreading. Regulation 526.9.2 does not permit soldered (tinned) ends on multiwire, fine-wire and very-fine-wire conductors in screw terminals. Solder creeps under clamping pressure, so the connection loosens and heats up over time. This does not ban soldered joints in general, and a tin-plated ferrule is not the same thing. Crimp a ferrule or use a terminal rated for the conductor class. [1]
Conductor classes in practical terms
| Class (Table 52.4) | Construction | Typical examples (check the cable data) |
|---|---|---|
| Class 1 | Solid | Smaller sizes of twin and earth |
| Class 2 | Stranded, rigid | Larger twin and earth, meter tails, SWA cores |
| Class 5 | Flexible, fine wires | Appliance flex, many PV and battery DC cables |
| Class 6 | Very flexible, very fine wires | Highly flexible cables and some welding cables |
Class describes construction, not quality. A terminal rated for 16 mm² Class 2 does not automatically take 16 mm² Class 5, with or without a ferrule. Check the terminal data.
Frequently asked questions
Do all flexible conductors require ferrules?
The required preparation depends on the terminal, conductor and manufacturer instructions. Ferrules are not a universal requirement for every connection.
Is tightening a terminal harder always safer?
No. Under-tightening and over-tightening both cause faults. Set a calibrated torque driver inside the range on the manufacturer’s data sheet, and only re-torque where the manufacturer requires it.
Does continuity alone prove a reliable termination?
No. Conductor condition, insertion, clamping, identification and mechanical support also need appropriate inspection.
Related Tradefox learning
Sources and further reference
- BS 7671 2018 A4 2026 authorised IET VitalSource reader
- IET BS 7671 and current Amendment 4 guidance
- SELECT Amendment 4 conductor class and connections summary Printed page 6 discusses conductor classes and Regulation 526.9.1.
- BEAMA guidance on mechanical shear off connectors May 2026 Specific connector category; not a generic torque specification for screw terminals.
- WAGO Using ferrules
- Weidmuller Crimping making the perfect crimp connection
- IET Consumer units and protective devices FAQs Background for terminology and termination principles. Some FAQ provisions refer to older amendments; not used as the sole authority for current rules.