Tradefox Reference
Terminal torque settings.UK electrical equipment, by manufacturer.
Tightening torques for consumer units, protective devices, wiring accessories, switchgear, earthing, surge protection, EV chargers and solar, from 52 manufacturers. The figures are guidance taken from manufacturers’ published documents, and the instructions supplied with the product always come first. Not every product is listed: see No published figure for what we looked for and could not find. Every figure is graded by how well it is backed. Select a product for the conditions that apply and the source we checked.
Terminal torque settings by manufacturer
At a glance: 703 torque figures from 52 manufacturers, counted by category. These are counts, not settings. Turn on JavaScript to see each figure with its terminal, conditions and source.
| Manufacturer | Figures | By category |
|---|---|---|
| ABB | 45 | Consumer units & devices 11, Switchgear 31, Surge protection 3 |
| Andersen | 2 | EV chargers 2 |
| BG (Luceco) | 64 | Consumer units & devices 53, Earthing 1, Surge protection 10 |
| Chint | 5 | Consumer units & devices 5 |
| Click Scolmore | 37 | Consumer units & devices 9, Accessories 25, Switchgear 2, Surge protection 1 |
| Contactum | 14 | Consumer units & devices 7, Surge protection 7 |
| Crabtree | 19 | Consumer units & devices 6, Accessories 10, Switchgear 3 |
| DEHN | 8 | Surge protection 8 |
| Doepke | 4 | Consumer units & devices 4 |
| Easee | 1 | EV chargers 1 |
| Eaton | 56 | Consumer units & devices 23, Switchgear 33 |
| Enphase | 4 | Solar & batteries 4 |
| EO Charging | 1 | EV chargers 1 |
| ERIS / AER | 4 | Consumer units & devices 4 |
| Europa Components | 4 | Consumer units & devices 4 |
| Fox ESS | 2 | Solar & batteries 2 |
| Fronius | 1 | Solar & batteries 1 |
| Furse (ABB) | 11 | Earthing 6, Surge protection 5 |
| FuseBox | 38 | Consumer units & devices 26, Switchgear 4, Surge protection 8 |
| Garo | 1 | Consumer units & devices 1 |
| Greenbrook | 8 | Consumer units & devices 4, Earthing 4 |
| Growatt | 3 | Solar & batteries 3 |
| Hager | 95 | Consumer units & devices 51, Switchgear 29, Surge protection 15 |
| Hypervolt | 1 | EV chargers 1 |
| IMO | 2 | Solar & batteries 2 |
| Legrand | 9 | Consumer units & devices 8, Accessories 1 |
| Lewden | 23 | Consumer units & devices 14, Switchgear 5, Earthing 1, Surge protection 3 |
| Live Distribution | 4 | Consumer units & devices 4 |
| MK Electric | 16 | Consumer units & devices 16 |
| myenergi | 4 | EV chargers 1, Solar & batteries 3 |
| Niglon | 3 | Consumer units & devices 3 |
| Ohme | 1 | EV chargers 1 |
| Phoenix Contact | 4 | Surge protection 4 |
| Pod Point | 4 | EV chargers 4 |
| Proteus | 13 | Consumer units & devices 9, Switchgear 3, Surge protection 1 |
| Santon | 2 | Solar & batteries 2 |
| Schneider Electric | 55 | Consumer units & devices 36, Accessories 1, Switchgear 14, Surge protection 4 |
| Siemens | 38 | Consumer units & devices 16, Switchgear 21, Surge protection 1 |
| SMA | 3 | Solar & batteries 3 |
| SolarEdge | 1 | Solar & batteries 1 |
| SolaX | 2 | Solar & batteries 2 |
| Solis | 4 | Solar & batteries 4 |
| Stäubli | 5 | Solar & batteries 5 |
| Sungrow | 2 | Solar & batteries 2 |
| Tesla | 4 | EV chargers 1, Solar & batteries 3 |
| Timeguard | 6 | Consumer units & devices 6 |
| Unicrimp | 2 | Accessories 2 |
| Victron Energy | 6 | Solar & batteries 6 |
| WAGO | 2 | Accessories 2 |
| Wallbox | 2 | EV chargers 2 |
| WCED | 8 | Consumer units & devices 6, Surge protection 2 |
| Wylex (Electrium) | 50 | Consumer units & devices 42, Switchgear 3, Surge protection 5 |
The product in front of you wins. Manufacturers change terminals between versions, so the torque printed on the device, its label or its instructions always takes priority over this list. Where a figure has a condition, such as a conductor size or the incoming side only, it applies only in that case. Verified: we opened a copy of the manufacturer’s own document, on its website or a stockist’s, and it states this value as printed. It does not mean we or the manufacturer have tested it, or that it applies to every version of the product. Corroborated: more than one published source gives this value, but the manufacturer’s documents are not consistent, or we could not open one that settles it. Check manufacturer: not from a manufacturer’s instructions or datasheet. It comes from an informal manufacturer source, such as a blog post, and is shown only so you know a figure exists. Do not use it without checking the device or its instructions. All sources were checked on 20 November 2026. Source links open the document where it is published, on the manufacturer’s website or a stockist’s. Tradefox does not host these files and is not responsible for other websites. Linking to a document does not mean we endorse the site or its products.
Before you rely on a torque figure. Four things to know.
This list helps you find the right figure quickly. It does not replace the manufacturer’s instructions. A connection that is too loose can overheat. One that is too tight can crush the conductor or crack the terminal.
The device label wins
If the device, its label or its instructions give a torque, use that. Ranges change and terminals are redesigned, so an older or newer version may need a different figure from the one shown here.
Read the conditions
Many figures apply only in one case. It might be the incoming or outgoing side, one or two conductors, a conductor size, or solid or stranded conductors. Check the terminal and conductor shown with each figure before you use it.
Use a torque screwdriver
Set a calibrated, insulated torque screwdriver to the figure and tighten until it clicks or slips. Never use a drill driver or impact driver on terminals. Give each conductor a firm tug afterwards to check it is held.
Isolate and prove dead
Safely isolate and lock off before you touch a terminal. Prove dead with a GS38-compliant voltage indicator: check it on a known live source, test, then check it on the known source again.
We opened a copy of the manufacturer’s own document, on its website or a stockist’s, and it states this value as printed. It does not mean we or the manufacturer have tested it, or that it applies to every version of the product.
More than one published source gives this value, but the manufacturer’s documents are not consistent, or we could not open one that settles it.
Not from a manufacturer’s instructions or datasheet. It comes from an informal manufacturer source, such as a blog post, and is shown only so you know a figure exists. Do not use it without checking the device or its instructions.
Where manufacturers’ documents disagree. Follow the one supplied with the product.
Sometimes a maker’s own documents give different figures for the same device. We show both rather than pick one. Use the instructions that came with the product in front of you, or ask the manufacturer.
ABB
ABB white paper 1SDC007406G0902 gives 9 Nm (M8) for Tmax XT2–XT4 rear terminals, while rear-terminal leaflet 1SDH000719 gives 6 Nm for every position.
BG (Luceco)
Fortress CU leaflets (CFSIL/A, CFUGA2IL/D, NXFUSE) give 3.5 Nm for the switch disconnector, but the 2025/2026 SPCDOC sheets and the 2023 Fortress catalogue give 2.5 Nm.
The CUSPDT21 SPD PE terminal is 2.0 Nm in leaflet BG_IM_CUSPDT21_B but 3 Nm in technical sheet SPCDOC 20230125.
Chint
The Chint NB1-63 catalogue prints 2.0 N·m beside 22 in-lb, while the GB product page for NB1-63H/2 and the NB1-63H datasheet give 2.5 N·m (22 in-lb).
Click Scolmore
The Polar PRW036 datasheet gives 2.5 Nm and the Mode CMA036 datasheet gives 2 Nm, though both are 13A 2G DP sockets with Ø5 mm terminals.
Contactum
Leaflet T2C4011-BKIT REV6 gives the T2C4011-B SPD as L 1.2 / PE 2 Nm and the busbar-fed T2C4011-BKIT as L 2 / PE 1.2 Nm.
Crabtree
Crabtree's 2010 catalogue gives 2.5…3 Nm for Starbreaker MCBs and 2 Nm for RCBOs, while catalogue B2600b (04/22) gives 2.3 min / 3.0 max and 1.2 min / 2.0 max (load terminal).
The Instinct CR1008 fan isolator datasheet gives 2.5 Nm, five times the 0.5 Nm on Instinct 10AX plate switch datasheets (CR1171 etc.) for the same conductors.
DEHN
DEHN leaflets give the remote signalling contact as 0.2 Nm in the metric section but 3 lbs-in (about 0.34 Nm) in the UL section of the same document.
Eaton
The 2009 Memera leaflet IL01900001U gives 2.5 Nm for RCD/RCBO terminals, above the 2.4 Nm maximum (2.0 Nm recommended) in the 2012 catalogue PG00400018U.
Catalogue CA132061EN prints M10 at 56 Nm for the EBF3 screw terminal but M10 at 32 Nm for EBF2, and M12 at 56 Nm for the lateral terminal.
NZM2-XKA tunnel terminals are 14 Nm in leaflet IL01206006Z (12/24) but 30 Nm in North American leaflet IL012099ZU (01/24) for the same conductor range.
NZM integrated auxiliary terminals are given as 1.2 Nm on page 3 and 1.3 Nm on page 4 of the same NZM leaflets.
Hager
Hager's Torque Settings sheet and the CDA263U product page give 2.8 Nm for RCCBs, but the Design 10/30/50/EVO consumer unit instructions (ZD0820, ZD0831, ZD0904/ZD0905) give 3.3 Nm.
Hager's UK product-support table gives 2.1 Nm for AFDDs, while the Design CU instructions give 3.5 Nm line / 2.4 Nm load and the ARR920U datasheet gives 2.40 Nm top / 3.50 Nm bottom.
Hager SPN instruction sheets 6S5052E and 6S5051G give 4 Nm (PZ2) for SPN SPDs, but the SPN115R, SPN140D and SPN715D product pages give 3.6 Nm.
For the JKA board 100 A switch-disconnector, ZD0651 Issue 4 gives 3.6 Nm and another copy of the instructions (Mastertrade) gives 3.3 Nm.
The Invicta 3 incomer leaflet ZD0680 Issue 12 says 3.6 Nm in the text and 3.5 Nm on the diagram; Issue 13 gives 3.5 Nm.
For NH1 fuse switches, the LT150 product page gives 20 Nm while the older 87578-0300 NH1–3 leaflet gives 12 Nm.
The JGxxxIN isolator instructions give 2.5 / 2 / 2 Nm (L/N/E) for the 2P 32 A, while the JG232IN datasheet gives a single nominal 2.50 Nm.
MK Electric
Current Sentry RCBO datasheets give a single 2.5 Nm, leaflet 52778PL gives 1.2–1.5 Nm load / 2.0–2.5 Nm supply, and older leaflet 43060PL gives 1.5 Nm load / 2.5 Nm supply.
The Sentry enclosure kit leaflet 45998PL gives 2–2.5 Nm for RCDs and MCBs, below the 3 Nm in the Sentry MCB and RCD datasheets.
myenergi
zappi installation instructions Rev 1.0 (2020) give 1.2 Nm for the supply terminals with 10 mm strip, while the v2.1 Quick Install Guide Rev 2.1.3 (2023) gives no terminal torque and an 18 mm strip.
Proteus
The Proteus catalogue (MP247) gives RCBO max 2 Nm and RCD max 2.5 Nm, while the ABX board leaflet PIIL001 gives RCBO line 2.5 Nm and RCD 2 Nm.
Siemens
The LV10 catalogue gives 2.5…3.5 Nm for 5SV RCCBs, while the 5SV3314-6GV01 datasheet gives 2.5…3 Nm.
5SU1 RCBO datasheets (5SU1356-7GV06, 5SU1353-1KK10) give 2.5…3 Nm, but LV10 (10/2021) gives 2.0 Nm for the new 5SU1 up to 32 A.
Wylex (Electrium)
RCBO outgoing torque is 2.5 Nm in the older Flexible Split Load leaflet B3349-15 but 2.0 Nm in current leaflets B3349-NS_8, LF1686-2, LF1546-2 and LF1514_4.
No published figure. What we looked for and could not find.
For these products we found no published terminal torque. Check the label inside the enclosure and the instruction leaflet, then ask the manufacturer. If a product isn’t listed, ask the manufacturer.
- ABBConsumer units & devices
No torque found for F200 Type A RCCBs or for any UK ABB consumer unit (enclosure, bars, main switch); eCatalog, RS and Farnell copies omit it.
- ABBSwitchgear
No leaflet found for Tmax XT6 and XT7; Tmax XT FC Cu / FC CuAl terminal values could not be tied to a terminal or cable size.
- ABBSurge protection
OVR T2 1N 40-275 P QS datasheet gives strip length (12.5 mm) but no torque.
- BG (Luceco)Consumer units & devices
No torque for the older Nexus SPD range (CUSPD1110/2070/2110/2405) or a stand-alone datasheet for the Fortress switch disconnector.
- BG (Luceco)Accessories
No published terminal torque for Nexus, Evolve or White Moulded accessories; datasheets give capacities and approx. 12 mm strip only.
- ChintConsumer units & devices
No torque for NX3 consumer units or the NL1 RCCB; the NX3 datasheet says only that screws should be tightened reliably.
- Clamp Co, Davico, Hager, Wiska, Unicrimp, ThorsmanEarthing
No published torque for BS 951 earth clamps from these makers; only Greenbrook publishes one.
- Click ScolmoreAccessories
No Definity-specific datasheet found, so Definity values are unconfirmed; ceiling roses (PRC001, PRC1440) give no torque.
- ContactumConsumer units & devices
Defender 2.0 instructions and AFDD leaflets refer to the label inside the enclosure or on the device; no published value for Type A RCDs (CPR…A), CPD isolators or the neutral/earth bars.
- CrabtreeConsumer units & devices
No torque for Starbreaker RCCBs, main switches, the miniature SPD, CU earth/neutral bars or Loadstar/Powerstar boards; checked the 2022 Starbreaker and Distribution Boards catalogues, SPD brochure and Electrium product sheets.
- CrabtreeAccessories
No published terminal torque for the Capital range (Instinct values are listed).
- EatonConsumer units & devices
No stand-alone Memshield 3 MCB/RCBO datasheet with a torque and no current Memera 2000 / Memshield 3 consumer unit leaflet; the Memshield 3 400 A panelboard leaflet (LT1209) values could not be tied to terminals.
- ESR, Mutec, Protek, Fusetek, Volex, WessexConsumer units & devices
No manufacturer document with terminal torque found for these consumer unit brands after several searches each.
- Furse (ABB)Earthing
No torque for type E U-bolt rod clamps (CR305–CR326) or the second type A list (CR205–CR230); GUV datasheet gives spanner sizes only.
- Furse (ABB)Surge protection
No torque for ESP M2/M4 or ESP D1 SPDs, and none in the ESP M1R manual pages read.
- FuseBoxSwitchgear
No termination data for stand-alone TPN isolators TPNI032–TPNI125.
- FusestarSwitchgear
No Fusestar torque document found online. Check the leaflet supplied with the switchfuse or ask Fusestar.
- GaroConsumer units & devices
No torque for the G6EV40PME EV consumer unit; datasheet and DoC give terminal size only.
- GivEnergy, Huawei, Sigenergy, Tesla, Fronius, EnphaseSolar & batteries
No terminal torque in text for GivEnergy inverters and batteries, Huawei SUN2000-L1 or Sigenergy (values only in figures), Tesla Powerwall 3 / Gateway 3 UK, Fronius Primo (label only), or Enphase field-wireable connectors; also none for battery, CT and PV terminals on Fox ESS, Solis, Growatt and SolaX, or for Lewden PV AC isolators.
- HagerAccessories
No published terminal torque for Sollysta, Muse/Inspire or Ashley J803 accessories; leaflets give capacity and 10–12 mm strip only.
- HagerSwitchgear
fv+ NH fuse switch leaflets and the h3+ technical catalogue would not open; P160 cage terminals (HYS001H/HYS005H) give no torque.
- Hager, LewdenEarthing
No published torque for MET bars or Hager KM/KXB brass earth terminals; product pages give capacity only.
- Henley Products (W.T. Henley)Earthing
No Nm values for Henley connector blocks, MET bars or meter-tail connectors; Safe-T connectors use shear-off screws.
- IMO, Click Scolmore, LewdenSwitchgear
No published torque for IMO AC rotary isolators, Click Scolmore IP65/66 rotary isolators, Lewden metal-clad isolators and switch-fuses, or Lewden SLM meter isolators.
- Knightsbridge, Varilight, Hamilton Litestat, VolexAccessories
No published terminal torque; datasheets and leaflets give capacities or "do not overtighten" only.
- LegrandConsumer units & devices
No installation leaflet with torque found for Legrand UK metal consumer units (6076 xx).
- LegrandAccessories
No published terminal torque for Arteor (BS) or the Mallia/Obria 45A cooker units (Synergy sockets are listed).
- LewdenConsumer units & devices
No torque for current PRO-range MCBs, main switches (GMS1002P only in the isolator data), RCDs, E/N bars or stand-alone PRO SPDs; PRO datasheets and brochures give capacity only.
- MK ElectricConsumer units & devices
No torque for the Sentry SPD (H6820S) or current Sentry consumer unit / enclosure neutral and earth bars; datasheets give capacity only.
- MK ElectricAccessories
No published terminal torque for Logic Plus, Edge or Aspect; technical sheets give capacities and a 4 mm screwdriver only.
- myenergi, Ohme, Wallbox, Rolec, Indra, Alfen, ZaptecEV chargers
No supply-terminal torque for zappi v2.1, Ohme Home Pro (flying lead), Wallbox Pulsar Plus / Pulsar Max / Copper SB, Rolec WallPod, Indra Smart PRO (push-down terminals), Alfen Eve Pro-line / S-line or Zaptec Go (lever terminals).
- NiglonConsumer units & devices
No torque for Protego consumer units, main switch, SPD or E/N bars; product pages say only "high-torque terminals".
- ProteusConsumer units & devices
No domestic consumer unit leaflet with main switch, SPD or E/N bar values; only catalogue device maxima and the ABX board leaflet.
- Schneider ElectricConsumer units & devices
Square D KQ / iKQ, Quickline 2, Domae, Easy9+ consumer unit and Twinbreak values exist only as attachments to se.com FAQs (FA142859, FA175472, FA142903) that could not be opened.
- Schneider ElectricAccessories
No published terminal torque for Lisse; the AR1817 instructions say only that screws must be firmly tightened.
- Schneider ElectricSwitchgear
Isobar B, I-Line and Quadbreak values are on a sticker or in FAQ attachments only; NSXm lug/busbar connector (LV426961) torque not found.
- SiemensConsumer units & devices
No UK Siemens consumer unit or Sentron distribution board leaflet with torque values found.
- TimeguardConsumer units & devices
No torque for TX consumer unit main switches, E/N bars or enclosures (Deta DS 1670–1675); the TX3913 SPD sheet prints its torque line in mm², so no value was taken.
- Wiska, Marrbox, GreenbrookAccessories
No torque for Wiska Combi junction boxes, Marrbox or Greenbrook CHOC30A/SC terminal strips.
- Wylex (Electrium)Consumer units & devices
No device-level torque for current NH/NHRS consumer units, stand-alone RCCBs (WRS/WRDS), main switches (WS124) or the NMT2SPD3W/1 SPD; checked device datasheets, WY2604a and NH board catalogues (capacity only). Only CU leaflets give values.
What BS 7671 asks. Tight, secure and as the maker says.
The wiring regulations do not list torque figures. They point you to the manufacturer and expect every connection to stay sound. References are to BS 7671:2018+A4:2026.
134.1.1 Manufacturer’s instructions
Good workmanship and proper materials must be used, and equipment must be installed taking account of the manufacturer’s instructions. That is where the torque figure comes from.
526.1 Durable connections
Every connection must give durable electrical continuity and adequate mechanical strength and protection. Correct torque is how a screw terminal helps meet this.
526.3 Accessible for inspection
Connections must stay accessible for inspection, testing and maintenance, with a few listed exceptions such as joints designed to be buried or maintenance-free connectors.
EICR item 4.20 Connections
Item 4.20 on the EICR schedule of inspections covers conductor connections, including busbars. It asks you to confirm they are correctly located in terminals, tight and secure.
No figure for your device? Ask, don’t guess.
If the label, the enclosure sticker and the instruction leaflet give no torque, contact the manufacturer’s technical line before you terminate. BEAMA says its members provide torque settings with their products, so most will give you a figure.
Standard test torques are not installation figures. Product standards such as IEC 60947-1 and BS EN 60999-1 set the torques used to type-test screw terminals. They describe what a new terminal must withstand in a test, not how tight to make a connection. If you need them, they are in the standards themselves, available from BSI.
Unit conversion. Newton metres to other units.
UK and European instructions give torque in newton metres (Nm). Some tools and imported equipment use pound-force inches or kilogram-force centimetres. 1 Nm = 8.85 lbf·in = 10.2 kgf·cm.
| Nm | lbf·in | kgf·cm |
|---|---|---|
| 0.5 | 4.42 | 5.1 |
| 0.8 | 7.08 | 8.2 |
| 1 | 8.85 | 10.2 |
| 1.2 | 10.62 | 12.2 |
| 1.5 | 13.27 | 15.3 |
| 2 | 17.70 | 20.4 |
| 2.5 | 22.12 | 25.5 |
| 3 | 26.55 | 30.6 |
| 3.5 | 30.97 | 35.7 |
| 4 | 35.40 | 40.8 |
| 4.5 | 39.82 | 45.9 |
| 5 | 44.25 | 51.0 |
| 6 | 53.10 | 61.2 |
Torque screwdrivers. Only as good as their last calibration.
How accurate they are
ISO 6789-1 allows setting-type torque screwdrivers up to 10 Nm to read within ±6 % of the set value. Choose one whose range covers the figures you use most, with 1,000 V insulation to BS EN 60900.
When to recalibrate
Recalibrate after a drop, or if readings feel inconsistent. Norbar suggests you retest within 12 months or 5,000 uses, whichever comes first. Our torque tool calibration guide explains what is checked and how often.
Common questions. Short answers.
Use the figure for the exact device you are fitting; it is on the label or in the instructions. As a guide, many UK MCB and RCBO terminals are 2–3 Nm. Some RCBO outgoing terminals are 1.2 Nm, and main switches are often higher, for example 3.6 Nm on Hager consumer units. Values differ by brand, device and terminal, and sometimes by cable size. The IET notes that most consumer units now come with a torque setting sticker.
Not as a table of figures. Regulation 134.1.1 says equipment must be installed taking account of the manufacturer’s instructions. Regulation 510.3 says the same for selecting and erecting equipment. So the manufacturer’s torque figure is the one that applies. Regulation 526.1 requires every connection to give durable electrical continuity and adequate mechanical strength. Item 4.20 on the EICR schedule of inspections covers conductor connections, including busbars. It asks you to confirm they are correctly located in terminals, tight and secure.
No. Electrical Safety First and BEAMA guidance on consumer units says to use only power tools designed as torque drivers. An ordinary drill driver is not suitable. Use a torque screwdriver set to the manufacturer’s figure. Too loose, and the connection can overheat and arc. Too tight, and you can crush the conductor, which can then overheat or break.
Check the label inside the enclosure and the instruction leaflet first, then ask the manufacturer. BEAMA says its members provide torque settings with their products. Standard test torques in product standards such as IEC 60947-1 are used to test terminal strength. They are not installation figures, so ask the manufacturer.
Under ISO 6789-1:2017, a setting (click) type torque screwdriver working at 10 Nm or below must be within ±6 %. That covers the screwdrivers most electricians use. Norbar suggests you retest within 12 months or 5,000 uses, whichever comes first. Retest sooner if the tool has been dropped or its readings seem inconsistent.
Manufacturers revise figures between ranges and document issues. For example, Hager’s torque settings sheet gives 2.8 Nm for its RCCB. Its Design 10/30, 50 and EVO consumer unit instructions give 3.3 Nm. Where documents disagree, follow the instructions supplied with the product in front of you.
They should be checked. Electrical Safety First and BEAMA guidance says every termination in a consumer unit should be checked. That includes factory-made ones, at installation and at every periodic inspection. Safely isolate and prove dead before you touch any terminal.
Practise
Practise this in a simulation
Practise safe isolation and torquing consumer unit terminals on a virtual installation before you do it for real.
Take it with you: printable quick card (PDF) · all figures as a spreadsheet (CSV)
Spotted a wrong or out-of-date figure? Tell us which product it is and the document you checked, and we’ll review it.
Product and brand names are trademarks of their owners. Tradefox is not affiliated with or endorsed by any manufacturer listed. This page is general information for competent persons and is not a substitute for the manufacturer’s instructions, training or supervision. See our terms of use.