Installation design
Trunking space factor from cable diameters
- where
- total overall cable area (mm²)
- number of cables of each type
- overall cable diameter including insulation and sheath (mm)
- trunking internal area (mm²)
- internal width (mm)
- internal height (mm)
- space factor (%)
Explain this equation
Works out how full a trunking is from the outside diameters of the cables, for cables or trunking that the On-Site Guide factor tables do not cover.
d is the overall diameter of each cable including its insulation and sheath, from the manufacturer. W and H are the clear internal width and height of the trunking.
Each cable takes up a circle of area π d² ÷ 4. Add those up and divide by the inside area of the trunking to get the space factor. The On-Site Guide limit is 45%, leaving at least 55% free.
Sense check: ten cables of 3.6 mm diameter take about 102 mm², only 4% of a 50 × 50 mm trunking, which could take about 1,125 mm² of cable.
Watch out: use the overall diameter, not the conductor size. A 2.5 mm² single is much bigger than 2.5 mm² once the insulation is included.
For cables or trunking not covered by the factor tables (Tables E5 and E6 of the IET On-Site Guide), the space factor should not exceed 45% of the net internal cross-sectional area of the trunking. The space factor is the total overall cross-sectional area of the cables, including insulation and any sheath, as a percentage of that internal area.
The area of each round cable is π d² / 4 from its overall diameter. Add them up and divide by the internal area of the trunking. The answer must be at or below the limit, leaving at least 55% free space.
Enter your values to see the result.
Common mistake
Using the conductor csa (for example 2.5 mm²) instead of the area from the cable's overall diameter.
Limits
Uses the internal dimensions you enter: deduct lids, dividers and lips. For conduit the equivalent fallback limit is 35%. Not a check of current-carrying capacity or grouping.
Sources
- IET Wiring Matters (November 2021): The history of cable capacities for conduit and trunking (total cable factor must be less than the conduit or trunking factor; 35% conduit, 45% trunking space factors)
- IET Engineering Communities forum (quoting the On-Site Guide): Space factor for single cables inside trunking (On-Site Guide: space factor not to exceed 45% of the net internal cross-sectional area)
The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.