Installation design

Trunking space factor from cable diameters

Ac=π4(n1d12+n2d22)At=W×HSF=AcAt×100
where
Ac
total overall cable area (mm²)
ni
number of cables of each type
di
overall cable diameter including insulation and sheath (mm)
At
trunking internal area (mm²)
W
internal width (mm)
H
internal height (mm)
SF
space factor (%)
Explain this equation

Works out how full a trunking is from the outside diameters of the cables, for cables or trunking that the On-Site Guide factor tables do not cover.

d is the overall diameter of each cable including its insulation and sheath, from the manufacturer. W and H are the clear internal width and height of the trunking.

Each cable takes up a circle of area π d² ÷ 4. Add those up and divide by the inside area of the trunking to get the space factor. The On-Site Guide limit is 45%, leaving at least 55% free.

Sense check: ten cables of 3.6 mm diameter take about 102 mm², only 4% of a 50 × 50 mm trunking, which could take about 1,125 mm² of cable.

Watch out: use the overall diameter, not the conductor size. A 2.5 mm² single is much bigger than 2.5 mm² once the insulation is included.

For cables or trunking not covered by the factor tables (Tables E5 and E6 of the IET On-Site Guide), the space factor should not exceed 45% of the net internal cross-sectional area of the trunking. The space factor is the total overall cross-sectional area of the cables, including insulation and any sheath, as a percentage of that internal area.

The area of each round cable is π d² / 4 from its overall diameter. Add them up and divide by the internal area of the trunking. The answer must be at or below the limit, leaving at least 55% free space.

count
count
%

Enter your values to see the result.

Common mistake

Using the conductor csa (for example 2.5 mm²) instead of the area from the cable's overall diameter.

Limits

Uses the internal dimensions you enter: deduct lids, dividers and lips. For conduit the equivalent fallback limit is 35%. Not a check of current-carrying capacity or grouping.

Sources

The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.