Installation design
Conduit or trunking capacity from cable factors
- where
- total cable factor
- number of cables of each type
- cable factor for that cable type
- conduit or trunking factor
- spare factor
- share of the enclosure factor used (%)
Explain this equation
Checks whether a set of cables will fit in a conduit or trunking using the On-Site Guide unit factor method, and how much room is left.
Each cable size has a cable factor and each conduit or trunking size has a factor, from the tables in Appendix E of the IET On-Site Guide. n is how many of each cable you are installing.
A cable factor is a number that represents the space the cable needs, so the factors simply add up. The enclosure factor already allows for free space and for drawing the cables in, so the total only has to come in under it.
Sense check: six 4 mm² stranded cables at 58 each total 348. A 16 mm conduit (290) is too small; a 20 mm conduit (460) takes them with 112 to spare.
Watch out: the conduit tables are different for short straight runs and for long runs or runs with bends. Use the one that matches the run.
Checks whether a group of cables will fit a conduit or trunking using the unit factor method. Each cable size has a cable factor and each conduit or trunking size has a factor, taken from the tables in Appendix E of the IET On-Site Guide (or IET Guidance Note 1, or the manufacturer). Multiply each cable factor by the number of those cables, add them up, and the total must be no more than the enclosure factor.
The conduit tables differ for short straight runs and for longer runs or runs with bends, so take the factors from the table that matches the run. Enter up to three cable types.
Enter your values to see the result.
Common mistake
Taking the conduit factor from the short straight-run table for a long run with bends.
Limits
Arithmetic only: you must enter the factors from the current tables for your cable type, conduit length and number of bends. Space for drawing in is not the same as current-carrying capacity: apply grouping factors to the cables separately.
Sources
- Voltimum / Marshall-Tufflex: Spacing factors, a brief guide (cable factors from the IET On-Site Guide; 6 × 4 mm² = 348, choose 20 mm conduit)
- IET Wiring Matters (November 2021): The history of cable capacities for conduit and trunking (total cable factor must be less than the conduit or trunking factor; 35% conduit, 45% trunking space factors)
The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.