Testing and verification

Measured earth fault loop impedance check (0.8 rule)

Zs(m)≤0.8×Cmin×U0IaMargin=0.8×Cmin×U0Ia−Zs(m)
where
Zs(m)
measured earth fault loop impedance (Ω)
Cmin
minimum voltage factor, 0.95
U0
nominal voltage to Earth (V)
Ia
current that operates the device in the required time (A)
Margin
limit minus the reading (Ω); negative means too high
Explain this equation

Checks a measured earth fault loop impedance reading against the limit for a test done with the conductors cold, and shows how much margin is left.

Ia is the fault current that makes the device operate within the required disconnection time, read from its time/current curve or the manufacturer's data. U0 is 230 V on a normal UK supply. Cmin = 0.95 allows for the supply voltage being up to 5% low.

The design maximum is Cmin × U0 ÷ Ia: the reduced voltage divided by the impedance must still drive Ia. Conductors are hotter in service than when tested, which raises their resistance, so a cold reading is compared with 0.8 of the design maximum.

Sense check: for a 32 A Type B MCB the BS 7671 maximum is 1.37 Ω, so a cold reading should be no more than about 1.10 Ω (1.09 Ω unrounded). A reading of 1.25 Ω fails.

Watch out: using the device rating In instead of Ia gives a limit many times too high.

Checks a measured earth fault loop impedance reading against the limit for a cold test. The design maximum is Zs ≤ Cmin × U0 / Ia (Regulation 411.4.4 of BS 7671 transposed, with Cmin = 0.95). A test is done with the conductors at ambient temperature, but in service they run hotter and their resistance rises, so the reading is compared with 0.8 times the design maximum. This is how the values in the IET On-Site Guide and Guidance Note 3 are produced.

Ia is the current that makes the device operate within the required disconnection time. Read it from the device's time/current curve, the manufacturer's data or the curves in Appendix 3 of BS 7671. A positive margin means the reading is within the limit.

Enter your values to see the result.

Common mistake

Comparing a cold test reading with the full design maximum instead of the 0.8 value, or using the device rating In instead of Ia.

Limits

A comparison for TN systems with overcurrent protective devices. It does not check RCD protection, TT systems or cable thermal limits. Where the reading is over the limit but under the design maximum, investigate further rather than condemning the circuit. BS 7671:2018+A4:2026 is the current edition.