Installation design

Main protective bonding conductor size (where PME does not apply)

Sb=max(6,min(25,Se2))
where
Sb
minimum main protective bonding conductor csa, copper (mm²)
Se
csa required for the earthing conductor (mm²)
Explain this equation

Works out the minimum size of copper main protective bonding conductor where PME conditions do not apply, such as a TN-S or TT supply.

Se is the cross-sectional area required for the installation's earthing conductor. Sb is the bonding conductor to the gas, water and other extraneous-conductive-parts.

Regulation 544.1.1 sets the bonding conductor at half the earthing conductor, but never smaller than 6 mm² and never needing to be more than 25 mm² in copper. The result is a minimum, so round up to the next standard cable size.

Sense check: a 16 mm² earthing conductor gives 8 mm², so you would fit 10 mm². A 10 mm² earthing conductor gives 5 mm², raised to the 6 mm² minimum.

Watch out: on a PME (TN-C-S) supply this rule does not apply. Use Table 54.8, based on the supply neutral, which gives at least 10 mm².

Regulation 544.1.1 of BS 7671: where PME conditions do not apply (for example TN-S or TT), a copper main protective bonding conductor must be at least half the csa required for the earthing conductor of the installation, and not less than 6 mm². It need not exceed 25 mm² in copper.

The result is a minimum: choose the next standard size at or above it. For example, a 16 mm² earthing conductor gives 8 mm², so 10 mm² is used.

Enter your values to see the result.

Common mistake

Halving the line conductor (meter tail) instead of the earthing conductor, or using this rule on a PME supply.

Limits

Not for PME (TN-C-S) supplies: there the size comes from Table 54.8 of BS 7671 using the copper-equivalent csa of the supply neutral, with a minimum of 10 mm². Other metals need equivalent conductance. The distributor may require a larger size.

Sources

The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.