Installation design
Cooker circuit diversity
- where
- full-load current (A)
- total rated load of the cooker (W)
- supply voltage (V)
- assessed current demand after diversity (A)
- 1 if the cooker control unit has a socket outlet, otherwise 0
Explain this equation
Works out the current demand to design a household cooker circuit for, using the diversity allowance in the IET On-Site Guide.
P is the total rating of the oven, grill and hob. The full-load current I is P ÷ U at the 230 V nominal supply. If I is 10 A or less, the whole current is taken. s adds 5 A only when the cooker control unit has a 13 A socket outlet built in.
Not every ring and the oven are on full at the same time, and thermostats cycle. The On-Site Guide takes the first 10 A in full and only 30% of the rest.
Sense check: a 14 kW cooker at 230 V draws 60.9 A flat out, but is assessed at 10 + 15.3 + 5 = 30.3 A, so a 32 A device rather than 30 A.
Watch out: older books work at 240 V, which gives slightly lower currents. Follow the manufacturer's instructions where they ask for a particular circuit rating, and do not add the 5 A when there is no socket on the control unit.
Applies the allowance for diversity to a household cooking appliance: the first 10 A of the rated current, plus 30% of the remainder of the rated current, plus 5 A for the socket outlet of a cooker control unit if one is fitted. This is the assessment given in the IET On-Site Guide and repeated by NICEIC. If the rated current is 10 A or less, the whole current is taken.
It is used to estimate the current demand for choosing the protective device and cable. A 14 kW cooker at 230 V draws 60.9 A at full load but is assessed at 10 + 15.3 + 5 = 30.3 A, so it needs more than a 30 A device. NICEIC notes that a 30 A or 32 A rating is generally suitable at 230 V for a typical cooker with four rings, a grill and an oven.
Enter your values to see the result.
Common mistake
Adding the 5 A socket allowance when the control unit has no socket, or working at 240 V instead of the 230 V nominal supply.
Limits
Household cooking appliances only, and only this assessment method. Follow the appliance manufacturer's instructions where they specify a circuit rating. Cable selection still needs correction factors and voltage drop.
Sources
- NICEIC Connections, Winter 2005/06 (via Voltimum): household cooker maximum demand = first 10 A of rated current + 30% of the remainder + 5 A for a cooker control unit socket-outlet; 30 A or 32 A generally suitable at 230 V
- TLC Direct, The Electricians Guide (Whitfield) 6.5.2 Cooker circuits: worked example at 240 V, 14 kW = 58.3 A assessed at 29.5 A
The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.