Installation design

Cooker circuit diversity

I=PUId=min(I,10)+0.3max(0,I−10)+5s
where
I
full-load current (A)
P
total rated load of the cooker (W)
U
supply voltage (V)
Id
assessed current demand after diversity (A)
s
1 if the cooker control unit has a socket outlet, otherwise 0
Explain this equation

Works out the current demand to design a household cooker circuit for, using the diversity allowance in the IET On-Site Guide.

P is the total rating of the oven, grill and hob. The full-load current I is P ÷ U at the 230 V nominal supply. If I is 10 A or less, the whole current is taken. s adds 5 A only when the cooker control unit has a 13 A socket outlet built in.

Not every ring and the oven are on full at the same time, and thermostats cycle. The On-Site Guide takes the first 10 A in full and only 30% of the rest.

Sense check: a 14 kW cooker at 230 V draws 60.9 A flat out, but is assessed at 10 + 15.3 + 5 = 30.3 A, so a 32 A device rather than 30 A.

Watch out: older books work at 240 V, which gives slightly lower currents. Follow the manufacturer's instructions where they ask for a particular circuit rating, and do not add the 5 A when there is no socket on the control unit.

Applies the allowance for diversity to a household cooking appliance: the first 10 A of the rated current, plus 30% of the remainder of the rated current, plus 5 A for the socket outlet of a cooker control unit if one is fitted. This is the assessment given in the IET On-Site Guide and repeated by NICEIC. If the rated current is 10 A or less, the whole current is taken.

It is used to estimate the current demand for choosing the protective device and cable. A 14 kW cooker at 230 V draws 60.9 A at full load but is assessed at 10 + 15.3 + 5 = 30.3 A, so it needs more than a 30 A device. NICEIC notes that a 30 A or 32 A rating is generally suitable at 230 V for a typical cooker with four rings, a grill and an oven.

Enter your values to see the result.

Common mistake

Adding the 5 A socket allowance when the control unit has no socket, or working at 240 V instead of the 230 V nominal supply.

Limits

Household cooking appliances only, and only this assessment method. Follow the appliance manufacturer's instructions where they specify a circuit rating. Cable selection still needs correction factors and voltage drop.

Sources

The tools calculate the displayed equation. They do not automatically choose cable sizes, approve installations, supply current regulatory tables, certify equipment or replace inspection and testing.