Performance

Refrigerant mass flow from capacity

m˙=Qh1−h4
where
ṁ
refrigerant mass flow (kg/s)
Q
refrigeration capacity (kW)
h1
enthalpy leaving the evaporator (kJ/kg)
h4
enthalpy entering the evaporator (kJ/kg)
Explain this equation

Works out how much refrigerant must circulate to give a required cooling capacity. Use it for sizing pipework and checking compressor selections.

Each kilogram of refrigerant absorbs h₁ − h₄ in the evaporator. Dividing the required capacity in kW (kJ/s) by that gives kilograms per second; the calculator also multiplies by 3600 for kg per hour.

This is the capacity equation rearranged for mass flow.

Sense check: 7.5 kW with 150 kJ/kg of refrigerating effect needs 0.05 kg/s, 180 kg/h.

Watch out: the refrigerating effect depends strongly on the condensing temperature and subcooling, so take h₄ at the real operating conditions.

Works out the refrigerant mass flow needed for a given cooling capacity, for line sizing, valve selection and velocity checks.

kJ/kg
kJ/kg

Enter your values to see the result.

Good to know

Q in kW divided by kJ/kg gives kg/s. Feed the result into the pipe velocity check with the density at line conditions.

Common mistake

Using compressor power instead of evaporator capacity, or condenser enthalpies.

Limits

Steady-state energy balance.