Psychrometrics

Moisture content (humidity ratio) from relative humidity

pws=0.61094·exp(17.625·tt+243.04)pw=RH100pwsW=621.945pwp−pw
where
pws
saturation vapour pressure, Magnus (kPa)
t
dry-bulb temperature (°C)
pw
partial pressure of water vapour (kPa)
RH
relative humidity (%)
W
moisture content (g/kg dry air)
p
atmospheric pressure (kPa)
Explain this equation

Converts a thermometer and hygrometer reading into moisture content, the actual amount of water in the air. Use it before latent load or mixing calculations.

p_ws is the most vapour the air could hold at temperature t. RH/100 times that gives p_w, the vapour pressure actually present. p is atmospheric pressure, and p − p_w is the pressure of the dry air. W is grams of water per kilogram of dry air.

The ratio of partial pressures is the ratio of molecules; 0.621945 converts that to a mass ratio because water molecules are lighter than air, and the 1000 gives g/kg.

Sense check: 20 °C at 50 % is about 7.2 g/kg; 30 °C saturated is about 27 g/kg.

Watch out: lower pressure at altitude gives a slightly higher moisture content for the same RH.

Converts a temperature and relative humidity reading into moisture content (grams of water per kilogram of dry air), the quantity used for latent loads and mixing.

°C
%

Enter your values to see the result.

Good to know

621.945 is 1000 × 0.621945, the ratio of the molar masses of water and dry air, giving g/kg. Standard pressure is 101.325 kPa; it falls about 1.2 kPa per 100 m of altitude. At 20 °C and 50 % RH the moisture content is about 7.2 g/kg.

Common mistake

Treating RH as a measure of how much water is in the air. Warm air at 40 % can hold more water than cool air at 90 %.

Limits

Magnus saturation pressure (within about 0.4 % from −40 to 50 °C) and no enhancement factor, so results are about 0.5 % below ASHRAE table values.

Sources