Fabric heat loss through an element (Q = U A ΔT)

Q=UA(ti−te)
where
Q
fabric heat loss (W)
U
U-value of the element (W/m²·K)
A
area of the element (m²)
ti
internal design temperature (°C)
te
external design temperature (°C)
Explain this equation

Works out the heat lost through one building element, such as a wall, roof or window, at the design outside temperature. Add up every element in a room, then add ventilation loss, to size a heat emitter.

U is how easily heat passes through one square metre of the element for each degree of temperature difference. A is its area. t_i − t_e is how much warmer inside is than outside.

Conducted heat is proportional to area and to the temperature difference, and the U-value bundles together the thermal resistance of every layer and its surfaces.

Sense check: a 20 m² modern wall at U = 0.28 with a 24 K difference loses about 134 W. A single-glazed window (U about 5) loses roughly eighteen times more per square metre.

Watch out: walls to unheated spaces or ground floors see a smaller temperature difference than outside walls, so use adjusted values from BS EN 12831-1.

Heat lost by conduction through one wall, roof, floor or window at design conditions. Add the elements up for a room, then add ventilation loss.

W/(m²·K)
m²
°C
°C

Enter your values to see the result.

Good to know

Use the element’s U-value from the specification or a BS EN ISO 6946 calculation. External design temperatures for UK locations are given in CIBSE Guide A; BS EN 12831-1 sets out the full method, including adjustments for ground floors and unheated spaces. Internal design temperatures are typically 18–21 °C for living spaces.

Common mistake

Using the full outside temperature difference for elements next to unheated spaces or the ground, which overstates their loss.

Limits

Steady-state one-dimensional conduction. Thermal bridges, ground-floor corrections and adjacent-space temperatures are not included; see BS EN 12831-1.

Sources

Results are calculations from the published methods and figures shown, and depend on the data you enter. Follow the equipment manufacturer’s data, CIBSE guidance, BS EN 378, the F-gas Regulations and your company procedures. Refrigerant work needs the correct F-gas certification.