F-gas

F-gas leak-check frequency (GB)

CO2e=m×GWP1000
where
CO₂e
CO₂ equivalent (tonnes)
m
refrigerant charge (kg)
GWP
global warming potential (AR4)
Explain this equation

Works out the CO₂ equivalent of a system and then the maximum time allowed between F-gas leak checks in Great Britain. Use it when setting up a maintenance schedule.

The charge in kilograms times the GWP, divided by 1000, gives tonnes of CO₂ equivalent. The interval then comes from the regulation bands: under 5 t no mandatory check; 5 to 50 t every 12 months; 50 to 500 t every 6 months; 500 t and over every 3 months. A working automatic leak detection system doubles each interval, and hermetically sealed, labelled systems under 10 t are exempt.

The CO₂e equation sets the size of the system; the interval is a lookup against the legal thresholds rather than a formula.

Sense check: 10 kg of R404A is about 39 t, so a check every 12 months, or every 24 months with leak detection fitted.

Watch out: at 500 t and above leak detection is compulsory, not optional, and the detection system itself must be checked at least every 12 months.

Finds the maximum interval between mandatory leak checks for stationary refrigeration, air conditioning and heat pump equipment under the GB F-gas rules, from the charge and GWP.

kg
ratio
ratio
ratio

Enter your values to see the result.

Good to know

Bands (GB, checked November 2026): 5 to under 50 t CO₂e every 12 months; 50 to under 500 t every 6 months; 500 t and over every 3 months. A working automatic leak detection system doubles each interval, and is mandatory at 500 t and over. Hermetically sealed, labelled systems under 10 t are exempt. A repaired leak must be rechecked within one month. Keep records of every check. Defra confirmed no 2026 legislation changing the phasedown steps and the leak-check bands are unchanged.

Common mistake

Basing the band on kg instead of t CO₂e, or using the factory charge only and forgetting the additional field charge.

Limits

Covers stationary RAC and heat pump equipment in England, Scotland and Wales only (not switchgear, vehicles or ORC). Northern Ireland follows EU Regulation 2024/573, which keeps the same CO₂e bands but also requires checks on HFO (Annex II section 1) charges of 1 kg or more, so this calculator does not apply there. Check the current GOV.UK guidance as the GB rules are under review.