Dew point temperature from temperature and RH (Magnus)

γ=ln(RH100)+17.625t243.04+ttd=243.04γ17.625−γ
where
γ
intermediate Magnus term (dimensionless)
RH
relative humidity (%)
t
dry-bulb temperature (°C)
td
dew point temperature (°C)
Explain this equation

Gives the temperature at which water starts condensing out of the air. Use it to check insulation on chilled pipework and ducts, condensation risk on cold surfaces and coil behaviour.

γ combines the relative humidity RH with the temperature t in the Magnus form. t_d is the temperature at which the air's existing vapour pressure equals the saturation pressure.

The Magnus equation is easy to invert, so dew point follows directly without trial and error. The constants 17.625 and 243.04 °C fit it to measured saturation pressures.

Sense check: 20 °C at 50 % has a dew point of about 9.3 °C; at 100 % the dew point equals the air temperature. Lower RH means a lower dew point.

Watch out: keep cold surfaces a margin above the dew point; a surface just at it will still sweat in local humid pockets.

The temperature at which air starts to condense on a cold surface. Use it to check coil apparatus dew point, pipe or duct insulation and the risk of condensation on chilled surfaces.

°C
%

Enter your values to see the result.

Good to know

Any surface colder than the dew point will collect condensation: insulate chilled-water pipework, refrigerant suction lines and cold ducts so their outer surface stays above it. At 20 °C and 50 % RH the dew point is about 9.3 °C.

Common mistake

Treating a dew point below 0 °C as a frost point. Below freezing this gives the dew point over water; frost forms at a slightly higher temperature.

Limits

Magnus form with Alduchov–Eskridge constants; within about 0.35 °C from −40 to 50 °C.