Insulation

Thermal resistance of insulation T1 (IEC 60287-2-1)

T1=ρT2πln(1+2t1dc)
where
T₁
thermal resistance of the insulation per core (K·m/W)
ρT
thermal resistivity of the insulation (K·m/W)
t₁
insulation thickness between conductor and sheath, including semiconducting screens (mm)
dc
conductor diameter (mm)
Explain this equation

Gives the thermal resistance of the insulation between the conductor and the metallic screen of a single-core cable, the first thermal term in an IEC 60287 rating.

ρ_T is the thermal resistivity of the insulation material, t₁ the total thickness from conductor to sheath including both semiconducting screens, and d_c the conductor diameter.

Heat flows radially through a cylindrical shell, so the same log form as for electrical insulation resistance applies: ln of outer over inner diameter, here written as 1 + 2t₁/d_c. Dividing by 2π spreads it round the circumference.

An 11 kV XLPE core with 3.4 mm over a 20 mm conductor gives about 0.16 K·m/W; a 132 kV core with 18 mm over 30 mm about 0.44 K·m/W. At 30 W/m of conductor loss that is roughly 5 K and 13 K of temperature rise across the insulation.

For three-core cables a geometric factor is needed instead; this simple form is for single-core cables only.

Thermal resistance between conductor and metallic sheath/screen of a single-core cable, the T1 term of the IEC 60287 rating equation.

K·m/W

Enter your values to see the result.

Good to know

IEC 60287-2-1: for single-core cables t1 includes the semiconducting screens (they are treated as insulation thermally), and dc is the conductor diameter. Thermal resistivities from IEC 60287-2-1: XLPE and PE 3.5 K·m/W, EPR 3.5 K·m/W (up to 3 kV) / 5.0 K·m/W (above 3 kV), PVC 5.0 (up to 3 kV) / 6.0 (above), impregnated paper 6.0. For conductors with a longitudinal water-blocking or other layers, follow the standard.

Common mistake

Using only the main insulation thickness and leaving out the two semiconducting screens, which understates T1.

Limits

Single-core cables only. Three-core cables need the geometric factor G from IEC 60287-2-1. Steady state; no moisture migration.

Sources

For competent high-voltage engineers. Results are calculations from the published methods shown and depend entirely on the data you enter. They are not a substitute for a system study, manufacturer data, the applicable standards and Engineering Recommendations, or your organisation’s safety rules. Never use a result to justify working on or near live HV equipment.