Overhead lines

Medium line nominal-π: sending-end voltage and current

Z=(R+jX)lY=jB×10−6×lA=1+YZ2Vs=AVr+ZIrIs=Y(1+YZ4)Vr+AIr
where
Z
total series impedance per phase (Ω)
R
resistance per phase (Ω/km)
X
reactance per phase (Ω/km)
l
line length (km)
Y
total shunt admittance per phase (S)
B
shunt susceptance per phase (µS/km)
A
ABCD constant A (= D)
Vs, V_r
sending- and receiving-end phase voltage phasors (V)
Is, I_r
sending- and receiving-end current phasors (A)
Explain this equation

Gives sending-end voltage, current, power and regulation for a medium-length line (roughly 80–250 km) using the nominal-π equivalent. Use it for load-flow sense checks or for reactive planning on long 132 kV and 275/400 kV circuits.

Z is the total series impedance and Y the total shunt admittance; half of Y is placed at each end of the π. B is susceptance per km, ωC, in µS/km, so ×10⁻⁶ converts to siemens. A (equal to D) is the voltage ratio constant, and Y(1 + YZ/4) is the C constant of the ABCD set.

The sending-end quantities come straight from the two-port equations V_s = AV_r + BI_r and I_s = CV_r + DI_r with B = Z. Regulation uses the no-load receiving voltage |V_s|/|A|, because the shunt capacitance alone lifts the open-end voltage.

Sense check: A is slightly below 1 (about 0.97–0.99). On light load I_s can exceed I_r because of charging current. Glover’s 345 kV, 200 km example gives about 8.7 % regulation.

Watch out: above about 250 km use the exact hyperbolic model; the lumped π then loses accuracy.

Sending-end voltage, current and power of a medium-length line using the nominal-π ABCD constants, given the receiving-end load.

ratio
Ω/km
Ω/km
µS/km

Enter your values to see the result.

Good to know

The nominal π lumps half the line shunt admittance at each end. A = D = 1 + YZ/2, B = Z, C = Y(1 + YZ/4). Regulation uses the no-load receiving voltage |Vs|/|A|. Susceptance B = 2πfC: about 2.8–3.5 µS/km for overhead lines at 50 Hz.

Common mistake

Entering total line capacitance instead of susceptance per km, or forgetting that the no-load receiving voltage is |Vs|/|A|, not |Vs|.

Limits

Nominal-π model, accurate to about 250 km at 50 Hz for overhead lines. Balanced, fully transposed line; positive sequence; conductance neglected.

Sources

For competent high-voltage engineers. Results are calculations from the published methods shown and depend entirely on the data you enter. They are not a substitute for a system study, manufacturer data, the applicable standards and Engineering Recommendations, or your organisation’s safety rules. Never use a result to justify working on or near live HV equipment.