Electrode resistance

Horizontal buried conductor or strip (Dwight / Sunde)

a=d2000s=2hR=ρ2πL(ln2La+ln2Ls−2+sL−s24L2+s432L4)
where
a
conductor radius (m)
d
conductor diameter, or half the tape width (mm)
s
twice the burial depth (m)
h
burial depth (m)
R
conductor resistance to remote earth (Ω)
ρ
soil resistivity (Ω·m)
L
total conductor length (m)
Explain this equation

Gives the resistance of a straight buried horizontal conductor, such as bare copper laid with a cable, a tape tail from a substation or a single run of a ring.

a is the conductor radius (d in mm divided by 2000) and s is twice the burial depth, which places the image of the conductor above the ground surface. L is the total length. The two log terms describe the conductor's own field and the effect of its image, and the small s/L terms are end corrections.

The shape follows from Dwight's method of averaging the potential along a line source and its mirror image in the ground surface. Length dominates: resistance falls roughly as 1/L, with only a weak dependence on diameter and depth.

20 m of 10 mm conductor at 0.6 m in 100 Ω·m soil is about 8.4 Ω. The rough rule 2ρ/L gives 10 Ω, which is deliberately conservative.

Watch out: beyond about 60√ρ metres the conductor's own impedance stops the far end contributing, so very long runs give less benefit than the formula predicts.

Resistance of a straight horizontal wire, stranded conductor or tape buried at shallow depth, such as a cable-route earth or a ring tail.

Ω·m

Enter your values to see the result.

Good to know

Dwight’s formula for a buried horizontal wire (IEEE 142 Table 4-5), written here with the total length L and depth h. For L ≫ h it reduces to Sunde’s ρ/(πL)·[ln(2L/√(2ah)) − 1]. For flat tape use an equivalent diameter equal to half the tape width (equivalent radius = width/4), as in EREC S34 formula R7. The second output is the rough BS EN 50522 rule of thumb R ≈ 2ρ/L.

Common mistake

Assuming a very long buried conductor keeps reducing resistance. Beyond roughly 60√ρ metres its own series impedance limits the useful length at 50 Hz.

Limits

Uniform soil, straight conductor, L ≫ h and L ≫ d, resistive (low-frequency) behaviour only. BS 7430 gives an equivalent coefficient form (P, Q) for strips and other shapes; that table is not reproduced here. Bends, rings and stars need the shape-specific formulas.

Sources

For competent high-voltage engineers. Results are calculations from the published methods shown and depend entirely on the data you enter. They are not a substitute for a system study, manufacturer data, the applicable standards and Engineering Recommendations, or your organisation’s safety rules. Never use a result to justify working on or near live HV equipment.