CT knee-point voltage requirement

Isf=IfIsnIpnVk≥KIsf(Rct+2RL+Rr)
where
Isf
secondary fault current (A)
If
maximum through-fault current (A, entered in kA)
Isn
CT rated secondary current (A)
Ipn
CT rated primary current (A)
Vk
minimum knee-point voltage (V)
K
dimensioning factor from the relay manual
Rct
CT secondary winding resistance (Ω)
RL
lead resistance, one way (Ω)
Rr
relay burden resistance (Ω)
Explain this equation

Finds the minimum knee-point voltage a class PX CT needs so it does not saturate before the protection operates. Use it when specifying CTs or checking an existing CT against a new relay.

Isf is the fault current on the CT secondary. Rct is the CT’s own winding resistance, 2RL the go-and-return leads, Rr the relay. Their sum is the loop the CT must drive current round. K allows for DC offset and remanence and comes from the relay maker.

The CT must produce enough EMF to push the secondary fault current through the whole loop; that EMF has to stay below the knee point where the core saturates. Ohm’s law gives the steady value and K adds headroom for transients.

Sense check: 10 kA through a 400/1 CT gives 25 A secondary; with 3.1 Ω of loop and K = 2 the CT needs about 155 V.

Watch out: the fault current is entered in kA and multiplied by 1000 internally. Use 2RL for earth faults on a residual connection; RL alone is often used for phase faults.

Minimum knee-point voltage a class PX (or equivalent) CT needs so that it does not saturate before the protection operates, from the fault current, ratio and secondary loop resistance.

ratio
A

Enter your values to see the result.

Good to know

The factor K comes from the relay manufacturer and allows for DC offset and remanence; typical values are 1 to 2 for overcurrent, larger for differential or distance protection, or K = 1 with a stability voltage for high-impedance schemes. The 2RL term is the full loop for an earth fault with a residual connection; for phase faults on a star-connected CT set, RL alone is often used. Take Rct at 75 °C.

Common mistake

Using the CT rated secondary current instead of the fault current referred to the secondary, or omitting the CT’s own winding resistance.

Limits

Steady-state symmetrical requirement multiplied by an empirical factor; it is not a full transient (TPX/TPY) dimensioning to IEC 61869-2.

Sources

For competent high-voltage engineers. Results are calculations from the published methods shown and depend entirely on the data you enter. They are not a substitute for a system study, manufacturer data, the applicable standards and Engineering Recommendations, or your organisation’s safety rules. Never use a result to justify working on or near live HV equipment.