Touch and step

Body current from touch voltage (1000 Ω body)

IB=UTZB+Ra
where
IB
body current (shown in mA)
UT
touch voltage (V)
ZB
body impedance, 1000 Ω simplification (Ω)
Ra
additional series resistance of footwear and contact (Ω)
Explain this equation

Estimates the current through a person touching earthed metalwork at a given touch voltage, useful for explaining risk or comparing with IEC 60479-1 time–current zones.

UT is the touch voltage, ZB the body impedance and Ra any extra resistance in series, mainly shoes and the contact between feet and ground. ENA TS 41-24 takes 4 kΩ per shoe and about 3ρ per foot contact.

It is Ohm's law around the shock circuit. The 1000 Ω body impedance is the usual simplification; IEC 60479-1 shows the real value depends on voltage, current path, contact area and moisture.

233 V across 1000 Ω gives 233 mA; adding 2150 Ω for shoes on soil reduces it to about 74 mA. Doubling the touch voltage doubles the current.

Watch out: whether a current is dangerous depends on how long it flows; check against the IEC 60479-1 curves or use the permissible voltage limits.

Estimates the current through a person from a touch voltage, using a fixed body resistance plus any series resistance of shoes and ground contact.

Enter your values to see the result.

Good to know

1000 Ω is the simplified hand-to-feet body resistance used by IEEE 80 and often quoted from IEC 60479-1. In IEC 60479-1 the real body impedance depends on touch voltage, current path, contact area and moisture, and falls as voltage rises; for a share of the population it is below 1000 Ω at HV touch voltages, so this simplification can underestimate current. ENA TS 41-24 assumes 4 kΩ per shoe plus 3ρ per foot contact; for shoes on 100 Ω·m soil the series total is 2150 Ω.

Common mistake

Comparing the result with a fixed “safe” current without the duration. Fibrillation risk depends on both current and time (IEC 60479-1 Figure 20, curves c1–c3).

Limits

Linear resistive model with a constant body impedance (IEC 60479-1 simplification, not its voltage-dependent impedance tables). Does not assess fibrillation probability; use BS EN 50522 or IEEE 80 limits for design.

Sources

For competent high-voltage engineers. Results are calculations from the published methods shown and depend entirely on the data you enter. They are not a substitute for a system study, manufacturer data, the applicable standards and Engineering Recommendations, or your organisation’s safety rules. Never use a result to justify working on or near live HV equipment.