Protective-device let-through energy

I2t≤k2S2
where
I²t
device let-through energy (A²s)
k
material/temperature factor
S
conductor area (mm²)
Explain this equation

Checks whether a conductor can withstand the energy a protective device lets through during a fault. Use it with current-limiting fuses and circuit-breakers, where clearing times are very short.

I²t is the device's let-through energy in A²s, from manufacturer data at the relevant fault level. k is the material and insulation factor. S is the conductor area in mm². k²S² is the most energy the conductor can absorb without its insulation overheating. The calculator gives k²S² and the margin left after subtracting I²t.

Heating in a very short fault depends on I²t, and a conductor's ability to absorb it depends on k² times its area squared. If the device lets through less than the conductor can take, the conductor is protected.

2.5 mm² copper with k = 115 can withstand about 82,600 A²s, so a device letting through 50,000 A²s leaves a positive margin. Doubling the area quadruples the withstand.

Watch out: a negative margin means the conductor is not protected. Use the manufacturer's figure, not a guess. This is a thermal check only; breaking capacity and disconnection times are separate.

A current-limiting device changes the current waveform during interruption. Its published let-through energy can be compared directly with conductor withstand.

Use manufacturer data for the actual device, voltage and prospective fault current. The simple constant-current I² × t estimate is not a substitute for those data.

A√s/mm²
A²s

Enter your values to see the result.

Common mistake

Comparing an A²s energy figure with a current in A.

Limits

This is a thermal comparison only; device breaking capacity, selectivity and disconnection requirements remain separate.