AC power

Power factor from measured power

PF=PS
where
PF
power factor
P
active power (W)
S
apparent power (VA)
Explain this equation

Finds a load's power factor from measured active and apparent power. Use it to judge whether correction is worthwhile, or to explain why a load draws more current than its wattage suggests.

P is the active power in watts, the power actually used. S is the apparent power in VA, the voltage times the current supplied. PF is their ratio, a number from 0 to 1.

PF tells you what fraction of the supplied volt-amperes does useful work. For pure sine waves it equals cos φ, where φ is the phase shift between voltage and current. With harmonics present, P/S also captures the distortion, so it gives the true power factor.

8 kW out of 10 kVA gives 0.8. Resistive heating is close to 1. A lightly loaded induction motor can fall to 0.5 or lower. On a large installation, anything much under 0.9 is worth a look.

Watch out: use matching units, kW with kVA or W with VA. P can never be larger than S.

Power factor compares active power with apparent power. An importing load with 8 kW and 10 kVA has a power factor of 0.8.

With harmonics present, true power factor includes distortion as well as phase displacement. A cos φ reading alone may not describe the complete load.

Enter your values to see the result.

Common mistake

Use matching prefixes: kW/kVA or W/VA, never W/kVA.

Limits

Use RMS voltage and current. The cos φ form assumes sinusoidal voltage and current; for distorted waveforms use measured true power factor, P/S.

Sources