Subcooling by refrigerant
R-1234yf subcooling from liquid line pressure
- where
- absolute pressure (bar)
- liquid line gauge pressure (bar)
- atmospheric pressure (bar)
- saturation temperature (°C)
- table temperature at or below the reading (°C)
- table pressure at T₁ (bar abs)
- next table temperature above (°C)
- table pressure at T₂ (bar abs)
- subcooling (K)
- measured liquid line temperature (°C)
- subcooling in Fahrenheit degrees (°F)
Explain this equation
Works out how far the R-1234yf liquid line is below its condensing (saturation) temperature. Use it to check or set the charge on TXV and EEV systems and to make sure solid liquid reaches the expansion device.
The gauge reads pressure above the atmosphere, so P_atm is added to get the absolute pressure P_abs that the P-T table uses. T_sat is the temperature at which R-1234yf liquid starts to boil at that pressure; T_liq is the actual pipe temperature. Every kelvin the liquid sits below T_sat is a kelvin of subcooling. R-1234yf is a single substance, so it boils and condenses at one temperature for a given pressure.
Saturation pressure rises roughly exponentially with temperature, so ln P is close to a straight line against T over a few kelvin. The calculator finds the two table rows either side of your reading (T₁, P₁ and T₂, P₂) and interpolates in ln P, which is much more accurate than a straight line through the raw pressures. The 1.8 converts a kelvin difference into Fahrenheit degrees for US charging charts.
Sense check: an air-cooled condenser on a 25–30 °C day typically condenses around 40–45 °C, and 3–6 K of subcooling is a common target. Zero subcooling means vapour may reach the expansion device; 15 K or more means liquid is backing up in the condenser.
Watch out: measure pressure and temperature at the same point, shade the probe from the sun and the condenser air, and remember receivers hide subcooling at their outlet.
Works out R-1234yf subcooling from a liquid line gauge reading and a pipe temperature, using a built-in R-1234yf pressure-temperature table.
R-1234yf is a single-component refrigerant (no glide), so one saturation temperature applies at each pressure. Safety class A2L (lower toxicity, mildly flammable).
Enter your values to see the result.
Good to know
Measure at the condenser outlet or liquid service valve, with pressure and temperature taken at the same place. Charge TXV or EEV systems to the manufacturer’s target subcooling; 3–6 K is common for air conditioning. Systems with a liquid receiver usually show little subcooling at the receiver outlet even when correctly charged, so use the sight glass and manufacturer guidance there. Single-component HFO used in vehicle air conditioning and some chillers. Mildly flammable (A2L). Safety class A2L: lower toxicity, mildly flammable. Follow BS EN 378 charge limits, keep ignition sources away, use A2L-rated recovery machines, vacuum pumps and leak detectors, and ventilate the work area.
Common mistake
Reading discharge pressure instead of liquid pressure, or measuring the pipe temperature in direct sunlight or a hot condenser air stream.
Limits
Table range 0.62 to 11.84 bar absolute (-40 to 46.11 °C). Saturation temperatures are interpolated from the published table (ln P against T between rows); checked against published points within ±0.3 K. Accuracy depends on the gauge and probe; pressure drop between the gauge point and the probe point adds error.
Sources
- National Refrigerants: Refrigerant Reference Guide, 7th edition (2020), R-1234yf P-T chart (psig, 5 °F steps)
- Gas Servei: R-1234yf technical data sheet, pressure/temperature table (bar abs; used as independent test points)
- Chemours: Opteon YF safety data sheet (vapour pressure 5917.2 hPa at 20 °C; used as an independent test point)
- ANSI/ASHRAE Standard 34 and ISO 817: Designation and safety classification of refrigerants (A1, A2L, A3, B2L)
- ACHR News: Understanding superheat (superheat = measured vapour temperature − saturation temperature at the same point)
Results are calculations from the published methods and figures shown, and depend on the data you enter. Follow the equipment manufacturer’s data, CIBSE guidance, BS EN 378, the F-gas Regulations and your company procedures. Refrigerant work needs the correct F-gas certification.