Tradefox

Tradefox – Build Skills

Learn Construction

‹ All hvac and refrigeration calculators

Superheat by refrigerant

R-32 superheat from suction pressure

Pabs=Pg+PatmTsat=T1+(lnPabs−lnP1)(T2−T1)lnP2−lnP1SH=Tline−TsatSH°F=1.8×SH
where
Pabs
absolute pressure (bar)
Pg
suction gauge pressure (bar)
Patm
atmospheric pressure (bar)
Tsat
saturation temperature (°C)
T1
table temperature at or below the reading (°C)
P1
table pressure at T₁ (bar abs)
T2
next table temperature above (°C)
P2
table pressure at T₂ (bar abs)
SH
superheat (K)
Tline
measured suction line temperature (°C)
SH°F
superheat in Fahrenheit degrees (°F)
Explain this equation

Works out how far the R-32 suction vapour is above its boiling (saturation) temperature. Use it to set or check an expansion valve, to judge the charge on a fixed-orifice system and to make sure no liquid returns to the compressor.

The gauge reads pressure above the atmosphere, so P_atm is added to get the absolute pressure P_abs used in the P-T table. T_sat is the temperature at which the last drop of R-32 liquid boils off at that pressure; T_line is the measured pipe temperature. Any heat picked up after that point raises the vapour temperature, and the difference is the superheat. R-32 is a single substance, so it boils and condenses at one temperature for a given pressure.

Saturation pressure rises roughly exponentially with temperature, so ln P is close to a straight line against T over a few kelvin. The calculator finds the two table rows either side of your reading (T₁, P₁ and T₂, P₂) and interpolates in ln P, which is far closer than interpolating the raw pressures. The 1.8 converts the kelvin difference into Fahrenheit degrees for US charging charts.

Sense check: a comfort-cooling evaporator runs at roughly 2–8 °C saturated, and a TXV typically holds 4–8 K of superheat. Near zero means liquid may be getting back to the compressor; 15 K or more points to a starved evaporator.

Watch out: pressure and temperature must be read at the same point. At low suction pressures the atmospheric pressure matters: at 300 m altitude it is about 0.04 bar lower than at sea level.

Works out R-32 superheat from a suction gauge reading and a pipe temperature. The saturation temperature comes from a built-in R-32 pressure-temperature table, so you do not need a P-T chart.

R-32 is a single-component refrigerant (no glide), so one saturation temperature applies at each pressure. Safety class A2L (lower toxicity, mildly flammable).

°C

Enter your values to see the result.

Good to know

Read the suction pressure and the pipe temperature at the same point: evaporator outlet (at the expansion-valve bulb) for evaporator superheat, or the compressor inlet for total superheat. Gauges read pressure above atmosphere, so the atmospheric pressure is added; enter your local value at altitude or on a weather extreme (about 0.012 bar less per 100 m). Typical evaporator superheat with a TXV is around 4–8 K; fixed-orifice systems need the manufacturer’s charging chart. Single-component HFC used in most new split air conditioners and heat pumps. Higher discharge temperatures than R-410A. Safety class A2L: lower toxicity, mildly flammable. Follow BS EN 378 charge limits, keep ignition sources away, use A2L-rated recovery machines, vacuum pumps and leak detectors, and ventilate the work area.

Common mistake

Reading the pressure at the service valve while measuring temperature somewhere else, or taping the probe to uninsulated pipe in a warm air stream.

Limits

Table range 1.1 to 43.84 bar absolute (-50 to 65 °C). Saturation temperatures are interpolated from the published table (ln P against T between rows); checked against published points within ±0.3 K. Results are only as good as the gauge (±1–2% of full scale is common) and the probe. For gauge readings, the actual atmospheric pressure matters most at low suction pressures.

Sources

Results are calculations from the published methods and figures shown, and depend on the data you enter. Follow the equipment manufacturer’s data, CIBSE guidance, BS EN 378, the F-gas Regulations and your company procedures. Refrigerant work needs the correct F-gas certification.

Secret Link