Performance

Condensate flow from a cooling coil

m˙w=QLhfg×3600
where
ṁw
condensate flow (kg/h)
QL
latent cooling load (kW)
hfg
latent heat of vaporisation of water (kJ/kg)
Explain this equation

Estimates how much water a cooling coil produces from its latent load. Use it for sizing condensate drains and pumps.

Q_L is the part of the coil duty spent condensing moisture out of the air, in kW, which is kJ per second. Each kilogram of water condensed gives up h_fg. Dividing gives kilograms per second, and 3600 converts to per hour. One kilogram of water is about one litre.

An energy balance: latent heat removed equals water condensed times its latent heat.

Sense check: 3 kW of latent load produces about 4.4 litres an hour, roughly 105 litres in 24 hours of running.

Watch out: latent load varies hugely with the weather and room use, so size pumps for the peak, not the average.

Estimates how much water a cooling coil produces from its latent load, for sizing condensate drains and pumps.

kJ/kg

Enter your values to see the result.

Good to know

hfg is 2489 kJ/kg at 5 °C, 2477 kJ/kg at 10 °C and 2454 kJ/kg at 20 °C (NIST); the default 2477 suits a typical coil surface temperature of about 10 °C. One kg of water is about one litre. Get the latent load from the load calculation or the unit’s sensible/total capacity split.

Common mistake

Using the total cooling load instead of the latent part, which overstates the water by two to four times.

Limits

Steady-state; ignores re-evaporation and start-up. Size pumps with a margin as the manufacturer advises.