Heat loss

Heat loss through an element (Q = U × A × ΔT)

Q=UA(Ti−Te)
where
Q
heat loss (W)
U
U-value (W/m²K)
A
net area of the element (m²)
Ti
internal design temperature (°C)
Te
external design temperature (°C)
Explain this equation

Works out the heat flowing out through one wall, roof, floor or window at design conditions. Use it to show the effect of insulation in watts or to size heating.

U is the watts lost through one square metre for each degree of difference between inside and outside. Multiplying by the area and the temperature difference gives the total watts.

Steady-state conduction: heat flow is proportional to area, U-value and temperature difference.

Sense check: 20 m² of wall at U = 0.3 with 24 °C difference loses about 144 W; the same wall uninsulated at 2.0 loses 960 W.

Watch out: use the net area with windows and doors taken out, and add those separately with their own U-values.

Steady-state fabric heat loss through one wall, roof, floor or window on a design day, for comparing before and after insulation or sizing emitters.

W/m²K
m²
°C
°C

Enter your values to see the result.

Good to know

This is the transmission term of the BS EN 12831 heat-load method. Use the net area (gross wall minus windows and doors, which you calculate separately with their own U-values). External design temperatures depend on location and are published in CIBSE Guide A and the MCS heat-pump tools, typically between about −1 °C and −5 °C in the UK. Living rooms are usually designed at 21 °C, bedrooms at 18 °C. Ventilation heat loss and thermal bridges at junctions are extra.

Common mistake

Using gross wall area and then adding windows too, so the window area is counted twice.

Limits

Steady state, one element, no thermal bridging at junctions (ψ-values), no ventilation or infiltration loss. For floors on the ground use the ISO 13370 U-value with the external temperature, as an approximation.