System checks

Superheat from suction line temperature

SH=Tline−Tsat
where
SH
superheat (K)
Tline
measured suction line temperature (°C)
Tsat
saturated suction temperature from the pressure (°C)
Explain this equation

Works out the superheat at the evaporator outlet or compressor inlet. Use it when setting or checking a TXV, judging the charge on a fixed-orifice system, or making sure no liquid is getting back to the compressor.

T_sat is the boiling temperature of the refrigerant at the suction pressure you measured, read from a P-T chart. T_line is the actual pipe temperature. Once all the liquid has boiled off, any further heat pickup raises the vapour temperature above T_sat, and that rise is the superheat.

A simple difference: how far the vapour is above its boiling point at that pressure.

Sense check: 5 °C saturated and 12 °C on the pipe gives 7 K. Typical TXV settings are around 4 to 8 K at the evaporator; much higher suggests undercharge or a starved coil, near zero suggests flooding.

Watch out: for zeotropic blends such as R407C use the dew point temperature for superheat. Insulate the probe and make good contact with the pipe.

Works out superheat: how far the suction vapour is above its boiling (saturation) temperature. Use it to set or check an expansion valve and to protect the compressor from liquid.

°C
°C

Enter your values to see the result.

Good to know

Read pressure and temperature at the same point. Evaporator superheat is taken at the evaporator outlet (TXV bulb position); total or compressor superheat at the compressor inlet. Typical evaporator settings are a few kelvin (often 4–8 K) but always use the equipment manufacturer’s figure. For zeotropic blends (R407C, R448A, R449A, R454 series) use the dew-point temperature at the suction pressure.

Common mistake

Using a bubble-point temperature for a blend, reading the pressure at a different point from the temperature, or clamping the probe on uninsulated pipe in a warm draught.

Limits

Simple temperature difference. Accuracy depends on the gauge, the probe and the P-T data used. Superheat is in kelvin (a temperature difference), not °C.

Sources

Results are calculations from the published methods and figures shown, and depend on the data you enter. Follow the equipment manufacturer’s data, CIBSE guidance, BS EN 378, the F-gas Regulations and your company procedures. Refrigerant work needs the correct F-gas certification.