Psychrometrics

Wet-bulb temperature from temperature and RH (Stull)

a1=arctan(0.151977(RH+8.313659)0.5)a2=arctan(t+RH)a3=arctan(RH−1.676331)a4=arctan(0.023101RH)Tw=ta1+a2−a3+0.00391838RH1.5a4−4.686035
where
a₁ … a₄
arctangent terms, in radians
RH
relative humidity (%)
t
dry-bulb temperature (°C)
Tw
wet-bulb temperature (°C)
Explain this equation

Estimates the wet-bulb temperature from a dry-bulb and RH reading. Use it for evaporative cooling and cooling tower checks or to compare with a sling psychrometer.

t is the dry-bulb temperature and RH the relative humidity in percent. The terms a₁ to a₄ are arctangent shapes, in radians, that together trace the true wet-bulb surface. T_w is the result.

Stull fitted this empirical equation to exact psychrometric results at sea-level pressure, so it avoids the trial-and-error the exact method needs.

Sense check: 20 °C at 50 % gives about 13.7 °C, a 6.3 K depression. At 100 % RH the wet bulb equals the dry bulb.

Watch out: the arctangents must be in radians, and the fit is less accurate below about 5 % RH or in cold, dry air.

Estimates the wet-bulb temperature from a dry-bulb and RH reading. Use it for cooling-tower and evaporative cooler checks or to compare with a sling psychrometer.

°C
%

Enter your values to see the result.

Good to know

The arctangents a1 to a4 are in radians (the × π/180 in the working converts from degrees). Stull’s fit is for standard sea-level pressure and has a typical error of under 0.3 °C. The wet-bulb depression (t − Tw) shows how much evaporative cooling is available.

Common mistake

Using a calculator set to degrees for the arctangents, which gives a nonsense answer.

Limits

Fitted for 5–99 % RH and −20 to 50 °C at 101.325 kPa; errors from −1 to +0.65 °C, worst at low humidity and low temperature. For exact work use the ASHRAE psychrometric equations.

Sources

Results are calculations from the published methods and figures shown, and depend on the data you enter. Follow the equipment manufacturer’s data, CIBSE guidance, BS EN 378, the F-gas Regulations and your company procedures. Refrigerant work needs the correct F-gas certification.