Installation design

Voltage drop as a percentage

ΔU%=100×ΔUUn
where
ΔU%
voltage drop as a percentage (%)
ΔU
voltage drop (V)
Un
nominal voltage (V)
Explain this equation

Expresses a voltage drop as a percentage of the nominal voltage. Use it to compare a calculated drop with the design allowance.

ΔU is the voltage drop in volts. U_n is the nominal voltage of the circuit: 230 V for single-phase, or 400 V line-to-line for three-phase. ΔU% is the drop as a percentage.

Dividing by the nominal voltage gives a fraction, and the 100 turns it into a percentage. Percentages let you compare circuits at different voltages on the same footing.

4.6 V on 230 V is 2%. For installations fed from a public low-voltage supply, the usual guidance is around 3% for lighting and 5% for other uses, measured from the origin, but work to the allowance set for the project.

Watch out: match the voltage basis, so a three-phase line-to-line drop goes over 400 V, not 230 V. Include upstream drop when comparing with the total allowance.

Percentage drop expresses lost voltage relative to nominal circuit voltage. A 4.6 V drop on 230 V is 2%.

A design may allocate part of its total voltage-drop allowance to a submain and the remainder to a final circuit. Use the same voltage basis throughout.

Enter your values to see the result.

Common mistake

Using 230 V for a line-to-line 400 V drop.

Limits

Compare the result with the applicable project and regulatory allowance, including upstream drop. Equipment starting and operating requirements also matter.